Program Example - Mitsubishi FX3U-USB-BD User Manual

Melsec-f fx series programmable controllers
Hide thumbs Also See for FX3U-USB-BD:
Table of Contents

Advertisement

FX Series PLC User's Manual - Data Communication Edition
Inverter Communication

10.2.3 Program example

1. Writing parameters to an inverter while the PLC is in RUN mode
M8002
Initial pulse
M10
Driving of
write
instruction
M8029
Instruction execute
complete
*1.
When using an E500 Series inverter, use "H2" to specify computer link operation.
*2.
The FX
3G
FNC271
K0
H0FD
IVDR
FNC271
K0
H0FB
IVDR
FNC 12
MOV
FNC 12
MOV
FNC 12
MOV
FNC 12
MOV
FNC 12
MOV
FNC 12
MOV
FNC 12
MOV
FNC 12
MOV
FNC274
K0
*2
IVBWR
PLC does not support the IVBWR instruction. Use the IVWR instruction instead.
10 Practical Program Examples (for FX3G/FX3U/FX3UC PLCs)
SET
M10
The write
instruction
is driven
H9696
K1
*1
H0
K1
K1
D200
P
K12000
D201
P
K2
D202
P
K500
D203
P
K7
D204
P
K10
D205
P
K8
D206
P
K10
D207
P
K4
D200
K1
RST
M10
Driving of
write
instruction
10.2 Practical Example 2
The inverter is reset
Computer link operation
is specified
The maximum
frequency (Pr. 1) is
specified
The maximum
frequency (Pr. 1) is
set to "120 Hz"
The minimum
frequency (Pr. 2) is
specified
The minimum
frequency (Pr. 2) is
set to "5 Hz"
The acceleration time
(Pr. 7) is specified
The acceleration time
(Pr. 7) is set to "1 sec"
The deceleration time
(Pr. 8) is specified
The deceleration time
(Pr. 8) is set to "1 sec"
The parameters are written
all at once
D200 to D207
(Pr. 1, Pr. 2, Pr. 7 and Pr. 8)
A
B
C
D
E
F
G
H
I
Apx.
E-107

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents