Link Time - Mitsubishi FX3U-USB-BD User Manual

Melsec-f fx series programmable controllers
Hide thumbs Also See for FX3U-USB-BD:
Table of Contents

Advertisement

FX Series PLC User's Manual - Data Communication Edition
N:N Network
2.2.2

Link time

The link time indicates the cycle time in which link devices are updated.
The link time varies depending on the number of linked units (master station and slave stations) and the
number of linked devices as shown in the table below.
Number of
linked
stations
2
3
4
5
6
7
8
Pattern 0
0 bit-devices
4 word-devices
18
26
33
41
49
57
65
Pattern 1
32 bit-devices
4 word-devices
22
32
42
52
62
72
82
2 Specifications
2.2 Link Specifications
Unit: ms
Pattern 2
64 bit-devices
8 word-devices
34
50
66
83
99
115
131