FX Series PLC User's Manual - Data Communication Edition
Non-Protocol Communication (RS/RS2 Instruction)

12.4.9 Communication format setting [D8370, D8400 and D8420]

These devices set the communication format.
1. Detailed contents
These devices can set the data length, parity, baud rate, etc.
When communication port ch0 is used, D8370 sets the communication format.
When communication port ch1 is used, D8400 sets the communication format.
When communication port ch2 is used, D8420 sets the communication format.
The table below shows the contents of the communication format settings. Computer link setting is not
applicable for D8370, D8400.
Bit No.
b0
Data length
b1
b2
b3
b4
b5
b6
b7
*2
b8
*2
Terminator
b9
b10
b11
Control line
b12
b13
Sum check
*3
b14
Control proce-
b15
dure (CR, LF)
*1.
This setting is available only in FX
*2.
Make sure to set as "0" when using computer link.
*3.
Make sure to set as "0" when using non-protocol communication.
*4.
In RS2 instruction, up to four headers and up to four terminators can be set.
*5.
The control line is not available in FX
*6.
When executing non-protocol communication using RS2 instruction, add the sum check after the
terminators.
Make sure to set the terminators when adding the sum check.
2. Cautions on use
In FX
and FX
3G
3UC
In FX
PLCs, the communication format can be set only for ch1 and ch2 using parameters.
3G
Name
0 (bit = OFF)
b2, b1
(0, 0): Not provided
Parity
(0, 1): Odd
(1, 1): Even
Stop bit
b7, b6, b5, b4
(0, 0, 1, 1): 300
Baud rate
(0, 1, 0, 0): 600
(bps)
(0, 1, 0, 1): 1200
(0, 1, 1, 0): 2400
Header
Non-protocol
communica-
*5
tion
Computer link
Protocol
Non-protocol
communica-
tion
Computer link
3G
PLCs, the communication format can be set using parameters.
Contents
7-bit
1-bit
b7, b6, b5, b4
(0, 1, 1, 1): 4800
(1, 0, 0, 0): 9600
(1, 0, 0, 1): 19200
(1, 0, 1, 0): 38400
Not provided
Not provided
b12, b11, b10
(0, 0, 0): Not provided <RS-232C interface>
(0, 0, 1): Standard mode <RS-232C interface>
(0, 1, 0): Interlink mode <RS-232C interface>
(0, 1, 1): Modem mode <RS-232C interface>
(1, 1, 1): Communication in accordance with RS-485
<RS-485/RS-422 interface>
b12, b11, b10
(0, 0, 0): RS-485/RS-422 interface
(0, 1, 0): RS-232C interface
Not added
Not used
Non-protocol
CR, LF: Not used
(Format 1)
CR, LF: Not used
Computer link
(Format 1)
PLCs.
PLCs when ch0 is used. Set "(1, 1, 1)".
3G
12 Related Data
12.4 Details of Related Devices (RS2 Instruction)
1 (bit = ON)
8-bit
2-bit
*1
*4
Provided
*4
Provided
*6
Added
Used
CR, LF: Used
communica-
(Format 2)
tion
CR, LF: Used
(Format 4)
A
B
C
D
E
F
G
H
I
Apx.
F-95