Service Settings
10.3.1 Hot Water Settings
Anti-bacteria function
52
This section describes the options you can set in menus under the Hot Water menu
item.
When this function is active, the hot-water temperature is raised once in a 24-hour
period to a user-defined temperature and for a user-defined length of time. The con-
troller accomplishes this by temporarily raising the hot-water temperature setpoint.
The following parameters can be set:
Display text
Parameter
Duration
Start time
Temperature
EY.65.H4.02
Default value,
Description
range
Default value:
The period during which the water tem-
0.0 hours
perature will be maintained at the in-
creased level. If this parameter is set to
Range:
0, the anti-bacteria function is disabled
0-23:45 hours
Default value:
The time of day at which the temperature
23:00
starts to increase
Range:
0:00-23:45
Default value:
The hot-water temperature setpoint will
70 °C
be increased to this level
Range:
1-99 °C