10.4.7 Sensors

Cut-off time constant
Time constants
These constants are used for calculating the filtered temperature (see page 42). The
controller calculates filtered values of outdoor and/or room temperatures, depending
on what sensors are connected to the system.
Display text
Parameter
Tout circ. 1
Outdoor tem-
Tout circ. 2
perature, cir-
cuit 1 or 2
Troom circ. 1
Room tem-
Troom circ. 2
perature, cir-
cuit 1 or 2
These time constants are used to convert the input signals received from sensors con-
nected to the system.
Note:
Sensor time constants concern Pt 1000, ESMF and 0–10 V sensors. Pulse and digital
sensors are not affected by the time constants. See page 30 for information on sensor
setup.
Display text
Parameter
S1, S2, etc.
Sensor 1, sen-
sor 2, etc.
EY.65.H4.02
Default value,
Description
range
Default value:
Time constant for calculating filtered
4 h
outdoor temperature. The filtered tem-
perature is used to control summer cut-
Range:
off
1.0-50.0 h
Default value:
Time constant for calculating filtered
1 h
room temperature. Used to control sum-
mer cut-off
Range:
1.0-50.0 h
Default value,
Description
range
Default value:
Time constants for sensor inputs
Depends on
the type of
sensor used
Range:
The range 0-200 minutes is for outdoor
0-999 seconds
temperature sensors
or
0-200 minutes
Service Settings
71