Communication - Danfoss ECL 2000 User Manual

District heating temperature controller.
Hide thumbs Also See for ECL 2000:
Table of Contents

Advertisement

Service Settings
Mixing

10.4.6 Communication

70
Display text
Parameter
Difference
Figure 10. Heat circuit with mixing valve
When the ECL 2000 LON option is installed, this setting picture displays the con-
troller's LON address and allows you to activate the service pin.
Display text
Parameter
Subnet
Node
LON
Service
EY.65.H4.02
Default value,
Description
range
Default value:
The minimum difference between the
5 K
temperature setpoint for a main heat
exchanger and the setpoint for a
Range:
mixing circuit connected to the heat
0-30 K
exchanger (S1 and S4 in the example
in Figure 10)
Default value,
Description
range
Default:
Read-only parameter. A value of 0
For LON module
means that the Subnet part of the
TP/XF-78: 12
controller's LON address is unde-
For LON module
fined
FTT-10F: 11
Range:
0, 1 – 255
Default:
Read-only parameter. A value of 0
For LON module
means that the Node part of the con-
TP/XF-78: 12
troller's LON address is undefined
For LON module
FTT-10F: 11
Range:
0, 1 – 127
Range:
Read-only parameter. The 48 bit id of
0000 0000 0000 –
the Neuron chip on the ECL 2000's
FFFF FFFF FFFF
LON module. A value of
0000 0000 0000 indicates that the
LON option is not installed
Press
i.e. make the ECL 2000 transmit its
LON neuron id onto the network
to activate the service pin,