5 SETTINGS
The wiring connection for two examples above is applicable to both form-A contacts with voltage monitoring and
solid-state contact with voltage monitoring.
NOTE

PATH: SETTINGS
CONTROL ELEMENTS
 COUNTER 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
There are 8 identical digital counters, numbered from 1 to 8. A digital counter counts the number of state transitions from
Logic 0 to Logic 1. The counter is used to count operations such as the pickups of an element, the changes of state of an
external contact (e.g. breaker auxiliary switch), or pulses from a watt-hour meter.
GE Multilin
Figure 5–37: TRIP CIRCUIT EXAMPLE 2


DIGITAL COUNTERS

COUNTER 1(8)
COUNTER 1
FUNCTION: Disabled
COUNTER 1 NAME:
Counter 1
COUNTER 1 UNITS:
COUNTER 1 PRESET:
0
COUNTER 1 COMPARE:
0
COUNTER 1 UP:
Off
COUNTER 1 DOWN:
Off
COUNTER 1 BLOCK:
Off
CNT1 SET TO PRESET:
Off
COUNTER 1 RESET:
Off
COUNT1 FREEZE/RESET:
Off
COUNT1 FREEZE/COUNT:
Off
C30 Controller System
5.6 CONTROL ELEMENTS
5.6.4 DIGITAL COUNTERS
Range: Disabled, Enabled
Range: 12 alphanumeric characters
Range: 6 alphanumeric characters
Range: –2,147,483,648 to +2,147,483,647
Range: –2,147,483,648 to +2,147,483,647
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
5
5-97