5 SETTINGS
The report control configuration settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
 REPORT 1
 CONFIGURATION
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Changes to the report configuration take effect when the C30 is restarted.
Disconnect any IEC 61850 client connection to the C30 prior to making setting changes to the report configuration.
Disconnecting the rear Ethernet connection from the C30 disconnects the IEC 61850 client connection.
NOTE
The breaker configuration settings are shown below. Changes to these values will not take effect until the UR is restarted:
PATH: SETTINGS
PRODUCT SETUP
 XCBR
 CONFIGURATION
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The
setting represents the breaker operating counter. As breakers operate by opening and closing, the
CLEAR XCBR1 OpCnt
XCBR operating counter status attribute (OpCnt) increments with every operation. Frequent breaker operation may result
in very large OpCnt values over time. This setting allows the OpCnt to be reset to "0" for XCBR1.
GE Multilin


COMMUNICATIONS
IEC 61850...
REPORT 1
RptID:
REPORT 1
OptFlds:
0
REPORT 1
BufTm:
0
REPORT 1
TrgOps:
0
REPORT 1
IntgPd:


COMMUNICATIONS
IEC 61850 PROTOCOL
XCBR1 ST.LOC OPERAND
Off
XCBR2 ST.LOC OPERAND
Off
XCBR6 ST.LOC OPERAND
Off
CLEAR XCBR1 OpCnt:
No
CLEAR XCBR2 OpCnt:
No
CLEAR XCBR6 OpCnt:
No
C30 Controller System

REPORT...
REPORT 1(6) CONFIGURATION
Range: up to 66 alphanumeric characters
Range: 0 to 65535 in steps of 1
Range: 0 to 4294967295 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 4294967295 in steps of 1
0

XCBR CONFIGURATION
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: No, Yes
Range: No, Yes
Range: No, Yes
5.2 PRODUCT SETUP