5.2 PRODUCT SETUP
5
The C30 supports the Distributed Network Protocol (DNP) version 3.0. The C30 can be used as a DNP slave device con-
nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the C30 maintains two sets of DNP
data change buffers and connection information, two DNP masters can actively communicate with the C30 at one time.
The IEC 60870-5-104 and DNP protocols cannot be simultaneously. When the IEC 60870-5-104 FUNCTION set-
ting is set to "Enabled", the DNP protocol will not be operational. When this setting is changed it will not become
NOTE
active until power to the relay has been cycled (off-to-on).
5-14
DNP PF SCALE
MESSAGE
FACTOR: 1
DNP OTHER SCALE
MESSAGE
FACTOR: 1
DNP CURRENT DEFAULT
MESSAGE
DEADBAND: 30000
DNP VOLTAGE DEFAULT
MESSAGE
DEADBAND: 30000
DNP POWER DEFAULT
MESSAGE
DEADBAND: 30000
DNP ENERGY DEFAULT
MESSAGE
DEADBAND: 30000
DNP PF DEFAULT
MESSAGE
DEADBAND: 30000
DNP OTHER DEFAULT
MESSAGE
DEADBAND: 30000
DNP TIME SYNC IIN
MESSAGE
PERIOD: 1440 min
DNP MESSAGE FRAGMENT
MESSAGE
SIZE: 240
DNP OBJECT 1
MESSAGE
DEFAULT VARIATION: 2
DNP OBJECT 2
MESSAGE
DEFAULT VARIATION: 2
DNP OBJECT 20
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 21
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 22
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 23
MESSAGE
DEFAULT VARIATION: 2
DNP OBJECT 30
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 32
MESSAGE
DEFAULT VARIATION: 1
DNP NUMBER OF PAIRED
MESSAGE
CONTROL POINTS: 0
DNP TCP CONNECTION
MESSAGE
TIMEOUT: 120 s
C30 Controller System
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 1 to 10080 min. in steps of 1
Range: 30 to 2048 in steps of 1
Range: 1, 2
Range: 1, 2
Range: 1, 2, 5, 6
Range: 1, 2, 9, 10
Range: 1, 2, 5, 6
Range: 1, 2, 5, 6
Range: 1, 2, 3, 4, 5
Range: 1, 2, 3, 4, 5, 7
Range: 0 to 32 in steps of 1
Range: 10 to 7200 s in steps of 1
5 SETTINGS