B.3 FILE TRANSFERS
APPENDIX B
B.3.2 MODBUS PASSWORD OPERATION
The D30 supports password entry from a local or remote connection.
Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry
and the faceplate RS232 connection. Remote access is defined as any access to settings or commands via any rear com-
munications port. This includes both Ethernet and RS485 connections. Any changes to the local or remote passwords
enables this functionality.
When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond-
ing connection password. If the connection is to the back of the D30, the remote password must be used. If the connection
is to the RS232 port of the faceplate, the local password must be used.
The command password is set up at memory location 4000. Storing a value of "0" removes command password protection.
When reading the password setting, the encrypted value (zero if no password is set) is returned. Command security is
B
required to change the command password. Similarly, the setting password is set up at memory location 4002. These are
the same settings and encrypted values found in the
menu via the
SETTINGS
PRODUCT SETUP
PASSWORD SECURITY
keypad. Enabling password security for the faceplate display will also enable it for Modbus, and vice-versa.
To gain command level security access, the command password must be entered at memory location 4008. To gain setting
level security access, the setting password must be entered at memory location 400A. The entered setting password must
match the current setting password setting, or must be zero, to change settings or download firmware.
Command and setting passwords each have a 30 minute timer. Each timer starts when you enter the particular password,
and is re-started whenever you use it. For example, writing a setting re-starts the setting password timer and writing a com-
mand register or forcing a coil re-starts the command password timer. The value read at memory location 4010 can be used
to confirm whether a command password is enabled or disabled (a value of 0 represents disabled). The value read at mem-
ory location 4011 can be used to confirm whether a setting password is enabled or disabled.
Command or setting password security access is restricted to the particular port or particular TCP/IP connection on which
the entry was made. Passwords must be entered when accessing the relay through other ports or connections, and the
passwords must be re-entered after disconnecting and re-connecting on TCP/IP.
B-8
D30 Line Distance Protection System
GE Multilin