5 SETTINGS
Multiple LANS, No Redundancy
The following topology provides local configuration/monitoring through EnerVista software on LAN1, to which port 1 (P1) is
connected, access to the public network on LAN2, to which port 2 (P2) is connected and communications with SCADA on
LAN3, to which port 3 (P3) is connected. There is no redundancy.
d) NETWORK
As outlined in the previous section, when using more than one Ethernet port, configure each to belong to a different net-
work or subnet using the IP addresses and mask.
PATH: SETTINGS
PRODUCT SETUP
 NETWORK PORT 1
MESSAGE
MESSAGE
MESSAGE
 NETWORK PORT 2
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
Figure 5–6: MULTIPLE LANS, NO REDUNDANCY


COMMUNICATIONS
NETWORK 1(3)
PRT1 IP ADDRESS:
0.0.0.0
PRT1 SUBNET IP MASK:
0.0.0.0
PRT1 GWY IP ADDRESS:
0.0.0.0
PRT1 GOOSE ENABLED:
Enabled
PRT2 IP ADDRESS:
0.0.0.0
PRT2 SUBNET IP MASK:
0.0.0.0
PRT2 GWY IP ADDRESS:
0.0.0.0
PRT2 REDUNDANCY:
No
PRT2 GOOSE ENABLED:
Enabled
D30 Line Distance Protection System
5.2 PRODUCT SETUP
Range: Standard IPV4 address format
Range: Standard IPV4 address format
Range: Standard IPV4 address format
Range: Enabled, Disabled
Range: Standard IPV4 address format
Range: Standard IPV4 address format
Range: Standard IPV4 address format
Range: No, Yes
Range: Enabled, Disabled