5.2 PRODUCT SETUP
The roles are defined as follows:
Administrator: Complete read and write access to all settings and commands. This role does not allow concurrent
access. This role has an operand to indicate when it is logged on.
Engineer: Complete read and write access to all settings and commands with the exception of configuring Security set-
tings and Firmware upgrades. This role does not allow concurrent access.
Operator: The Operator has read/write access to all settings under the command menu/section. This role does not
exist offline.
Supervisor: This is only an approving role. This role's authentication commits setting changes submitted by Administra-
tor or Engineer. The Supervisor role authenticates to unlock the UR relay for setting changes and not approve changes
after the fact. Only Supervisor can set the Settings and Firmware Lock in the Security Settings. This role also has the
ability to forcefully logoff any other role and clear the security event log. This role can also be disabled, but only
through a Supervisor authentication. When this role is disabled its permissions are assigned to the Administrator role.
Observer: This role has read only access to all UR settings. This role allows unlimited concurrent access but it has no
download access to any files on the device. Observer is the default role if no authentication has been done to the
device.
The Factory service role is not available and intended for factory use only.
c) LOCAL PASSWORDS
NOTE
PATH: SETTINGS
PRODUCT SETUP
 CHANGE LOCAL
 PASSWORDS
5
The Change Local Passwords menu is shown on the front panel and Enervista on a successful login of Administrator role.
The "login setting" in this menu is similar to the login setting described in PATH: SETTINGS > PRODUCT SETUP > SECU-
RITY except for the factory role.
Passwords are stored in text format. No encryption is applied.
Notes:
NOTE
In Local Authentication mode, the Observer role does not have a password associated with it. In Remote Authentica-
tion mode the Observer role requires a password.
The default password is "ChangeMe1#".
Once the passwords are set, the Administrator with Supervisor approval can change the role associated password.
In CyberSentry, password encryption is not supported.
d) SESSION SETTINGS
PATH: SETTINGS
PRODUCT SETUP
 SESSION
 SETTINGS
The following session settings are available.
5-14

SECURITY
CHANGE LOCAL PASSWORDS
LOGIN:
None
NEW PASSWORD:
MESSAGE
CONFIRM PASSWORD:
MESSAGE

SECURITY
SESSION SETTINGS
SESSION LOCKOUT:
3
SESSION LOCKOUT
MESSAGE
PERIOD: 3 min
D30 Line Distance Protection System
Range: 20 Alphanumeric Characters
Range: 20 Alphanumeric Characters
Range: 20 Alphanumeric Characters
Range: 0 to 99
Range: 0 to 9999 minutes
5 SETTINGS