GE D30 series Instruction Manual page 486

Line distance protection system. ur series
Hide thumbs Also See for D30 series:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 28 of 60)
ADDR
REGISTER NAME
63C1
Negative Sequence Instantaneous OC 1 Signal Source
63C2
Negative Sequence Instantaneous Overcurrent 1 Pickup
63C3
Negative Sequence Instantaneous Overcurrent 1 Delay
63C4
Negative Sequence Instantaneous OC 1 Reset Delay
63C5
Negative Sequence Instantaneous Overcurrent 1 Block
63C7
Negative Sequence Instantaneous Overcurrent 1 Target
63C8
Negative Sequence Instantaneous Overcurrent 1 Events
63C9
Reserved (8 items)
63D1
...Repeated for Negative Sequence Instantaneous OC 2
Negative Sequence Overvoltage (Read/Write Grouped Setting)
B
6440
Negative Sequence Overvoltage Function
6441
Negative Sequence Overvoltage Source
64A42
Negative Sequence Overvoltage Pickup
6443
Negative Sequence Overvoltage Pickup Delay
6444
Negative Sequence Overvoltage Reset Delay
6445
Negative Sequence Overvoltage Block
6447
Negative Sequence Overvoltage Target
6448
Negative Sequence Overvoltage Events
6449
...Repeated for module number 2
6452
...Repeated for module number 3
Power Swing Detect (Read/Write Grouped Setting)
65C0
Power Swing Detect Function
65C1
Power Swing Detect Source
65C2
Power Swing Detect Mode
65C3
Power Swing Detect Supervision
65C4
Power Swing Detect Forward Reach
65C5
Power Swing Detect Forward RCA
65C6
Power Swing Detect Reverse Reach
65C7
Power Swing Detect Reverse RCA
65C8
Power Swing Detect Outer Limit Angle
65C9
Power Swing Detect Middle Limit Angle
65CA
Power Swing Detect Inner Limit Angle
65CB
Power Swing Detect Delay 1 Pickup
65CC
Power Swing Detect Delay 1 Reset
65CD
Power Swing Detect Delay 2 Pickup
65CE
Power Swing Detect Delay 3 Pickup
65CF
Power Swing Detect Delay 4 Pickup
65D0
Power Swing Detect Seal In Delay
65D1
Power Swing Detect Trip Mode
65D2
Power Swing Detect Block
65D4
Power Swing Detect Target
65D5
Power Swing Detect Event
65D6
Power Swing Detect Shape
65D7
Power Swing Detect Quad Forward Middle
65D8
Power Swing Detect Quad Forward Outer
65D9
Power Swing Detect Quad Reverse Middle
65DA
Power Swing Detect Quad Reverse Outer
65DB
Power Swing Detect Outer Right Blinder
65DC
Power Swing Detect Outer Left Blinder
65DD
Power Swing Detect Middle Right Blinder
65DE
Power Swing Detect Middle Left Blinder
65DF
Power Swing Detect Inner Right Blinder
65E0
Power Swing Detect Inner Left Blinder
B-36
RANGE
0 to 5
0 to 30
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 1.25
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 5
0 to 1
0.05 to 30
0.1 to 500
40 to 90
0.1 to 500
40 to 90
40 to 140
40 to 140
40 to 140
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 1
0 to 4294967295
0 to 2
0 to 1
0 to 1
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
D30 Line Distance Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
1
F167
---
1
F513
pu
0.001
F001
ohms
0.01
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
degrees
1
F001
degrees
1
F001
degrees
1
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
---
1
F514
---
1
F300
---
1
F109
---
1
F102
---
1
F085
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
DEFAULT
0 (SRC 1)
1000
0
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
300
50
50
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0 (SRC 1)
0 (Two Step)
600
5000
75
5000
75
120
90
60
30
50
17
9
17
400
0 (Delayed)
0
0 (Self-reset)
0 (Disabled)
0 (Mho Shape)
6000
7000
6000
7000
10000
10000
10000
10000
10000
10000
GE Multilin

Advertisement

Table of Contents
loading