5.6 GROUPED ELEMENTS

PATH: SETTINGS
GROUPED ELEMENTS
 LINE PICKUP
5
The line pickup feature uses a combination of undercurrent and undervoltage to identify a line that has been de-energized
(line end open). Alternately, the user may assign a FlexLogic™ operand to the
minal status. Three instantaneous overcurrent elements are used to identify a previously de-energized line that has been
closed onto a fault. Faults other than close-in faults can be identified satisfactorily with the distance elements.
Co-ordination features are included to ensure satisfactory operation when high speed automatic reclosure (AR) is
employed. The
AR CO-ORD DELAY
reclose. Co-ordination is achieved by all of the
times out. The
CO-ORD DELAY
implemented.
The line pickup protection incorporates zone 1 extension capability. When the line is being re-energized from the local ter-
minal, pickup of an overreaching zone 2 or excessive phase current within eight power cycles after the autorecloser issues
a close command results in the
5-120
SETTING GROUP 1(6)
LINE PICKUP
FUNCTION: Disabled
LINE PICKUP SIGNAL
MESSAGE
SOURCE: SRC 1
PHASE IOC LINE
MESSAGE
PICKUP: 1.000 pu
LINE PICKUP UV PKP:
MESSAGE
0.700 pu
LINE END OPEN PICKUP
MESSAGE
DELAY:
0.150 s
LINE END OPEN RESET
MESSAGE
DELAY:
0.090 s
LINE PICKUP OV PKP
MESSAGE
DELAY:
0.040 s
AR CO-ORD BYPASS:
MESSAGE
Enabled
AR CO-ORD PICKUP
MESSAGE
DELAY:
0.045 s
AR CO-ORD RESET
MESSAGE
DELAY:
0.005 s
TERMINAL OPEN:
MESSAGE
Off
AR ACCELERATE:
MESSAGE
Off
LINE PICKUP DISTANCE
MESSAGE
TRIP: Enabled
LINE PICKUP BLOCK:
MESSAGE
Off
LINE PICKUP
MESSAGE
TARGET: Self-reset
LINE PICKUP
MESSAGE
EVENTS: Disabled
setting allows the overcurrent setting to be below the expected load current seen after
LINE PICKP UV
setting is normally enabled. It is disabled if high speed autoreclosure is
AR CO-ORD BYPASS
LINE PICKUP RCL TRIP
D30 Line Distance Protection System

LINE PICKUP
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: 0.000 to 30.000 pu in steps of 0.001
Range: 0.000 to 3.000 pu in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: Disabled, Enabled
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Disabled, Enabled
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
TERMINAL OPEN
elements resetting and blocking the trip path before the
FlexLogic™ operand. For security, the overcurrent trip is supervised
5 SETTINGS
5.6.3 LINE PICKUP
setting that specifies the ter-