GE D30 series Instruction Manual page 386

Line distance protection system. ur series
Hide thumbs Also See for D30 series:
Table of Contents

Advertisement

7.1 COMMANDS

PATH: COMMANDS
 COMMANDS
 CLEAR RECORDS
This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a com-
mand setting to "Yes" and pressing the ENTER key. After clearing data, the command setting automatically reverts to "No".

PATH: COMMANDS
 COMMANDS
 SET DATE AND TIME
7
The date and time can be entered here via the faceplate keypad, but if the relay is synchronizing to an external time source
such as PTP, IRIGB or SNTP, the manually entered time will be quickly over-written. The time setting is based on the 24-
hour clock. The complete date, as a minimum, must be entered to allow execution of this command. The new time (if
entered) and date will take effect at the moment the ENTER key is clicked.
The timescale of the entered time should be local time, including daylight time where and when applicable.
7-2
CLEAR RECORDS
CLEAR FAULT REPORTS?
No
CLEAR EVENT RECORDS?
No
CLEAR OSCILLOGRAPHY?
No
CLEAR BREAKER 1
ARCING AMPS? No
CLEAR BREAKER 2
ARCING AMPS? No
CLEAR UNAUTHORIZED
ACCESS? No
CLEAR DIRECT I/O
COUNTERS? No
CLEAR TELEPROTECT
COUNTERS? No
CLEAR ALL RELAY
RECORDS? No
SET DATE AND TIME
SET DATE AND TIME:
2000/01/14 13:47:03
D30 Line Distance Protection System
7 COMMANDS AND TARGETS
7.1.3 CLEAR RECORDS
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes. Valid only for units with Direct Input/
Output module.
Range: No, Yes
Range: No, Yes
7.1.4 SET DATE AND TIME
(YYYY/MM/DD HH:MM:SS)
GE Multilin