Resetting; Direct Inputs And Outputs - GE D30 series Instruction Manual

Line distance protection system. ur series
Hide thumbs Also See for D30 series:
Table of Contents

Advertisement

5 SETTINGS
b) USERST BIT PAIRS

PATH: SETTINGS
INPUTS/OUTPUTS
 REMOTE OUTPUTS
 UserSt- 1 BIT PAIR
MESSAGE
Remote outputs 1 to 32 originate as GSSE/GOOSE messages to be transmitted to remote devices. Each digital point in the
message must be programmed to carry the state of a specific FlexLogic operand. The setting above is used to select the
operand which represents a specific UserSt function (as selected by the user) to be transmitted.
The following setting represents the time between sending GSSE/GOOSE messages when there has been no change of
state of any selected digital point. This setting is located in the

COL
GSSE/GOOSE CONFIGURATION
For more information on GSSE/GOOSE messaging, refer to Remote Inputs/Outputs Overview in the Remote
Devices section.
NOTE

PATH: SETTINGS
INPUTS/OUTPUTS
 RESETTING
Some events can be programmed to latch the faceplate LED event indicators and the target message on the display. Once
set, the latching mechanism will hold all of the latched indicators or messages in the set state after the initiating condition
has cleared until a RESET command is received to return these latches (not including FlexLogic latches) to the reset state.
The RESET command can be sent from the faceplate Reset button, a remote device via a communications channel, or any
programmed operand.
When the RESET command is received by the relay, two FlexLogic operands are created. These operands, which are
stored as events, reset the latches if the initiating condition has cleared. The three sources of RESET commands each cre-
ate the
FlexLogic operand. Each individual source of a RESET command also creates its individual operand
RESET OP
,
RESET OP (PUSHBUTTON)
RESET OP (COMMS)
shown above selects the operand that will create the
a) DIRECT INPUTS

PATH: SETTINGS
INPUTS/OUTPUTS
 DIRECT INPUT
1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin

REMOTE OUTPUTS UserSt BIT PAIRS
UserSt- 1 OPERAND:
Off
UserSt- 1 EVENTS:
Disabled
PRODUCT SETUP
settings menu.
DEFAULT GSSE/GOOSE
UPDATE TIME: 60 s


RESETTING

RESET OPERAND:
Off
or
RESET OP (OPERAND)
RESET OP (OPERAND)

DIRECT INPUTS
DIRECT INPUT 1(32)
DIRECT INPUT
1
NAME: Dir Ip 1
DIRECT INPUT
1
DEVICE ID: 1
DIRECT INPUT
1
BIT NUMBER:
1
DIRECT INPUT
1
DEFAULT STATE: Off
DIRECT INPUT
1
EVENTS: Disabled
D30 Line Distance Protection System
5.8 INPUTS AND OUTPUTS
REMOTE OUTPUTS UserSt- 1(32) BIT PAIR
Range: FlexLogic operand
Range: Disabled, Enabled


COMMUNICATIONS
Range: 1 to 60 s in steps of 1
Range: FlexLogic operand
to identify the source of the command. The setting
operand.

5.8.10 DIRECT INPUTS AND OUTPUTS

Range: up to 12 alphanumeric characters
Range: 1 to 16
Range: 1 to 32
Range: On, Off, Latest/On, Latest/Off
Range: Enabled, Disabled
IEC 61850 PROTO-
5.8.9 RESETTING
5
5-225