Resetting - GE F60 Instruction Manual

Ur series feeder protection system
Hide thumbs Also See for F60:
Table of Contents

Advertisement

5 SETTINGS
Remote outputs (1 to 32) are FlexLogic™ operands inserted into GSSE/GOOSE messages that are transmitted to remote
devices on a LAN. Each digital point in the message must be programmed to carry the state of a specific FlexLogic™ oper-
and. The above operand setting represents a specific DNA function (as shown in the following table) to be transmitted.
Table 5–28: IEC 61850 DNA ASSIGNMENTS
DNA
IEC 61850 DEFINITION
1
Test
2
ConfRev
b) USERST BIT PAIRS

PATH: SETTINGS
INPUTS/OUTPUTS
 REMOTE OUTPUTS
 UserSt- 1 BIT PAIR
MESSAGE
Remote outputs 1 to 32 originate as GSSE/GOOSE messages to be transmitted to remote devices. Each digital point in the
message must be programmed to carry the state of a specific FlexLogic™ operand. The setting above is used to select the
operand which represents a specific UserSt function (as selected by the user) to be transmitted.
The following setting represents the time between sending GSSE/GOOSE messages when there has been no change of
state of any selected digital point. This setting is located in the

COL
GSSE/GOOSE CONFIGURATION
For more information on GSSE/GOOSE messaging, refer to Remote Inputs/Outputs Overview in the
Remote Devices section.
NOTE

PATH: SETTINGS
INPUTS/OUTPUTS
 RESETTING
Some events can be programmed to latch the faceplate LED event indicators and the target message on the display. Once
set, the latching mechanism will hold all of the latched indicators or messages in the set state after the initiating condition
has cleared until a RESET command is received to return these latches (not including FlexLogic™ latches) to the reset
state. The RESET command can be sent from the faceplate Reset button, a remote device via a communications channel,
or any programmed operand.
When the RESET command is received by the relay, two FlexLogic™ operands are created. These operands, which are
stored as events, reset the latches if the initiating condition has cleared. The three sources of RESET commands each cre-
ate the
FlexLogic™ operand. Each individual source of a RESET command also creates its individual operand
RESET OP
,
RESET OP (PUSHBUTTON)
RESET OP (COMMS)
shown above selects the operand that will create the
GE Multilin
FLEXLOGIC™ OPERAND
IEC 61850 TEST MODE
IEC 61850 CONF REV

REMOTE OUTPUTS UserSt BIT PAIRS
UserSt- 1 OPERAND:
Off
UserSt- 1 EVENTS:
Disabled
PRODUCT SETUP
settings menu.
DEFAULT GSSE/GOOSE
UPDATE TIME: 60 s


RESETTING

RESET OPERAND:
Off
or
RESET OP (OPERAND)
RESET OP (OPERAND)
F60 Feeder Protection System
5.8 INPUTS/OUTPUTS
REMOTE OUTPUTS UserSt- 1(32) BIT PAIR
Range: FlexLogic™ operand
Range: Disabled, Enabled


COMMUNICATIONS
Range: 1 to 60 s in steps of 1
Range: FlexLogic™ operand
to identify the source of the command. The setting
operand.
IEC 61850 PROTO-
5
5.8.9 RESETTING
5-247

Advertisement

Table of Contents
loading

Table of Contents