3 Error Tables
Event code
Event name
80300000 hex
Safety Pro-
cess Data
Communica-
tions Timeout
84F1 0000 hex
NX Bus I/O
Communica-
tions Stopped
80220000 hex
NX Message
Communica-
tions Error
90400000 hex
Event Log
Cleared
90430000 hex
Memory All
Cleared
NX-series Load Cell Input Units
The section provides a table of errors (events) that can occur in the following Unit.
NX-RS
The manual names are given below for the catalog numbers given in the Reference column of the
event table.
Cat. No.
W565
Event code
Event name
00200000 hex
Non-volatile
Memory Hard-
ware Error
05120000 hex
A/D Conver-
sion Error
3-182
Meaning
Assumed cause
A communications
• A setting is not correct. The set-
timeout occurred in
ting of the safety task period is
safety process data
too short.
communications
• There is excessive noise.
with the Safety
• The Safety CPU Unit or safety
Control Unit.
slave entered a status where it
could not continue safety pro-
cess data communications.
• An error or status change
occurred in the Communica-
tions Coupler Unit to which the
Unit is connected, preventing
correct process data communi-
cations.
An error occurred in
There is a hardware error in the
I/O communications
Communications Coupler Unit or
between the Com-
an NX Unit.
munications Cou-
pler Unit and an NX
Unit.
An error was
• The message communications
detected in mes-
load is high.
sage communica-
• The communications cable is
tions for an NX Unit
disconnected or broken.
and the message
• Message communications were
frame was dis-
cut off as the result of executing
carded.
a synchronization or resto-
ration operation on the Sysmac
Studio or as the result of dis-
connecting an EtherCAT slave.
The event log was
The event log was cleared by the
cleared.
user.
The Unit settings
The Clear All Memory operation
were cleared.
was performed.
NX-series Load Cell Input Unit User's Manual
Meaning
Assumed cause
An error occurred in
• Non-volatile memory
non-volatile mem-
failure
ory.
AD conversion was
• EXC+ terminal and
not performed by
EXC- terminal are
the AD converter.
short-circuited.
• Noise
• A/D converter failure
Level
Maj
Prt
Min
S
S
Manual name
Level
Maj
Prt
Min
S
S
NJ/NX-series Troubleshooting Manual (W503)
Reference
Obs Info
Z930
Z930
S
Z930
S
Z930
S
Z930
Reference
Obs
Info
W565
W565