Description - GE C70 Instruction Manual

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

PRODUCT DESCRIPTION
Several options are available for communication. An RS232 port (USB port with the graphical front panel) can be used to
connect to a computer to program settings and monitor actual values. The rear RS485 port allows independent access by
operating and engineering staff. It can be connected to system computers with baud rates up to 115.2 kbps. All serial ports
use the Modbus RTU protocol. The IEC 60870-5-103 protocol is supported on the RS485 interface. Also only one of the DNP,
IEC 60870-5-103, and IEC 60870-5-104 protocols can be enabled at any time on the relay. When the IEC 60870-5-103
protocol is chosen, the RS485 port has a fixed even parity and the baud rate can be either 9.6 kbps or 19.2 kbps. The
100Base-FX or 100Base-TX Ethernet interface provides fast, reliable communications in noisy environments. The Ethernet
port supports IEC 61850, Modbus/TCP, TFTP, and PTP (according to IEEE Std. 1588-2008 or IEC 61588), and it allows access
2
to the relay via any standard web browser (C70 web pages). The IEC 60870-5-104 protocol is supported on the Ethernet
port. The Ethernet port also supports the Parallel Redundancy Protocol (PRP) of IEC 62439-3 (clause 4, 2012) when
purchased as an option.
Secure Routable GOOSE (R-GOOSE) is supported with software options.
Settings and actual values can be accessed from the front panel or EnerVista software.
The C70 uses flash memory technology that allows field upgrading as new features are added. Firmware and software are
upgradable.
The following single-line diagram illustrates the relay functionality using American National Standards Institute (ANSI)
device numbers.
Table 2-1: ANSI device numbers and functions supported
Device
Function
number
27P
Phase undervoltage
50BF
Breaker failure
50DD
Disturbance detector
50G
Ground instantaneous overcurrent
50N
Neutral instantaneous overcurrent
50P
Phase instantaneous overcurrent
50_2
Negative-sequence instantaneous overcurrent
51G
Ground time overcurrent
51N
Neutral time overcurrent
51P
Phase time overcurrent
51_2
Negative-sequence time overcurrent
59B
Bank phase overvoltage
2-2
Device
Function
number
59N
Neutral overvoltage
59NU
Neutral voltage unbalance
59P
Phase overvoltage
59X
Auxiliary overvoltage
59_2
Negative-sequence overvoltage
60N
Bank neutral current unbalance
60P
Bank phase current unbalance
67N
Neutral directional overcurrent
67P
Phase directional overcurrent
67_2
Negative-sequence directional overcurrent
87V
Bank voltage differential