Vt And Ct Setup - GE C70 Instruction Manual

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

SETTINGS EXAMPLE
Based on the bank configuration, CT connections, and VTs connections, a C70 model is chosen with three CT/VT modules:
two type 8L modules (in slots F and U) and one type 8V module (in slot M) to provide following protection functionality.
Negative-sequence instantaneous overcurrent (ANSI 50_2) to provide fast backup protection against arcing within
capacitor bank
Phase overvoltage (ANSI 59B) to provide protection against overvoltages
Bank overcurrent protection, phase instantaneous overcurrent (ANSI 50P), neutral instantaneous overcurrent (ANSI
50N) and phase time overcurrent (ANSI 51P) to provide protection against major faults within the capacitor bank
Bank undervoltage (ANSI 27P) to detect loss of bus voltage and trip the bank
Voltage differential (ANSI 87V) to detect failure of one or more capacitor elements in a given string. Three voltage
differential elements can be set for this application: one between two tap voltages (ANSI 87V-1) and two between the
bus voltage and tap voltage in both strings (ANSI 87V-2 and 87V-3).
Phase current unbalance (ANSI 60P) to detect failure of one or more capacitor elements in a given string
8

8.4.2 VT and CT setup

The CT and VT connections are shown in the previous figure. The CT channels are connected as follows:
The type 8L CT/VT module F1 to F3 three-phase CT channels are connected to the bus side three-phase CTs with a
120 / 5 A ratio
The type 8L CT/VT module U1 to U3 three-phase CT channels are connected to the neutral side window CTs with a
50 / 5 A ratio
The following settings are applied in the EnerVista UR Setup software.
8-12
Figure 8-12: Sample capacitor bank configuration
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
CHAPTER 8: APPLICATION OF SETTINGS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents