CHAPTER 5: SETTINGS
R-RxGOOSE RECEPTION MODE specifies the R-RxGOOSE DST IP range. When set to SSM, R-RxGOOSE DST IP must be in
the range of 232.0.0.1 to 232.255.255.255. When set to ASM, R-RxGOOSE DST IP must be in the range of 224.0.0.1 to
239.255.255.255, excluding the SSM range. Note that the SSM range is inside the ASM range and therefore the ASM use
excludes the SSM range. The default destination IP address 224.0.0.0 is reserved, and hence not a valid multicast IP
address.
The reception modes are related to Layer-3 R-GOOSE reception from routers/WAN. The subscription to multicasting of R-
GOOSE is supported using IGMP Protocol Independent Multicast (PIM). It is made available in either Source Specific
Multicast (SSM) mode or Any Source Multicast (ASM) mode. Unicast (over UDP) mode can also be used. In case of
multicasting (IGMPv3 based SSM or ASM), the R-GOOSE subscriber device requests the Last Hop Router (LHR) to
subscribe to a specific multicasting group.
If the publisher is using a unicast destination IP address for this R-GOOSE, then set R-RxGOOSE1 RECEPTION MODE to
Unicast. Otherwise set R-RxGOOSE1 RECEPTION MODE to the SSM or ASM mode used by the local routers/firewalls.
R-RxGOOSE1 SRC IP
Range: 0.0.0.0 to 255.255.255 in steps of 1
Default: 127.0.0.1
When the RxGOOSE1 MODE setting is other than R-GOOSE, the value of this setting is not used. When the RxGOOSE1
MODE setting is R-GOOSE and the R-RxGOOSE RECEPTION MODE setting is ASM, the value of this setting is not used.
Otherwise the Source IP Address field of incoming R-GOOSE messages must exactly match this value for the message to
be accepted as a valid RxGOOSE1 message. Set this setting to the value of the source IP address used by the publisher.
For UR publishers, this value is in setting PRT# IP ADDRESS.
The UR does not validate the address entered. The default IP address 127.0.0.1 is a reserved, not a valid IP address. Enter
a valid IP source address.
R-RxGOOSE1 DST IP
Range: 0.0.0.0 to 255.255.255 in steps of 1
Default: 224.0.0.0
When the RxGOOSE1 MODE setting is other than R-GOOSE, the value of this setting is not used. Otherwise the
Destination IP Address field of incoming R GOOSE messages must exactly match this value for the message to be
accepted as a valid RxGOOSE1 message. Set this setting to the same value as the R-GOOSE publisher's Destination IP
Address. For UR publishers, this value is in setting R-TxGOOSE# DST IP.
The destination IP address needs to be a valid multicast or unicast IP address. The UR does not validate the address
entered. The default IP address 224.0.0.0 is reserved, and hence not a valid multicast IP address.
R-RxGOOSE1 SECURITY
Range: None, Signature, SignatureAndEncryption
Default: None
This setting specifies the level of security (authentication/encryption) used for RxGOOSE1. None indicates no security
mechanisms are in use. Signature indicates only signature (no encryption) is in use. SignatureAndEncryption indicates
that both signature and encryption are in use. Normally this setting is set to match the GOOSE publisher's security
method.
RxGOOSE1 Member 1
Range: End of List, BOOLEAN, FLOAT32, INT32, Dbpos (DPS), Quality, TimeStamp, Struct
Default: End of List
This setting specifies the type that the first member of incoming GOOSE messages must be for the message to be
accepted as a valid RxGOOSE1 message. There are similar settings for each of the up to 64 members that the UR is able
to subscribe to in a given GOOSE message. The member before the first member setting set to "End of List" must be the
last member of the message for the message to be accepted as a valid RxGOOSE1 message.
If the publisher is a UR 7.3x or 7.40 series device, set these settings to match the basic type of the members of the
publisher's data set selected by the publisher's TxGOOSE datSet setting.
If the publisher dataset includes members with structured data, that is, data attributes, sub-data objects, and/or data
attributes with sub-data attributes, configuration must use one of the new 7.40 UR Setup RxGOOSE Inputs pages. In this
case the Member setting displays as the product-related name used by the publishing IED of the data object or data
attribute, in standard SCSM format (e.g. Publisher1LD1/LLN0$ST$Off$stVal).
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
5
5-73

Hide quick links:

Advertisement

Table of Contents
loading