CHAPTER 5: SETTINGS
In the example shown, failure of any of the three Ethernet ports triggers the Product Information page to display. With
unauthorized access (such as wrong password), IRIG-B clock failure, or breaker trouble, the Event Records display. When a
breaker opens, a single-line diagram displays. For the Ethernet and IRIG-B failure operation to work, these functions also
have been enabled under Settings > Product Setup > User-Programmable Self Tests.
To use the feature, select a CONDITION, select an ACTIVATE PAGE, then save.
CONDITION
Range: OFF, ON, any FlexLogic operand
Default: OFF
Select the FlexLogic operand for the trigger. When it transitions from Off to On, it opens the page specified by the
ACTIVATE PAGE setting. The FlexLogic operands selectable depend on product. Select it from the drop-down list. Or click
or select the field and start typing to auto-fill. For example, typing F displays FIRST ETHERNET FAIL, while typing BR
displays the first breaker option.
ACTIVATE PAGE
Range: Product Information, SLD 1...5, Annunciator, Annunciator 1...8, Actual Values Phasors 1...6, Tabular 1...5, Event
Records, Targets
Default: Product Information
This setting specifies the page to display on the graphical front panel when the FlexLogic operand selected by its
CONDITON setting transitions from Off to On.
The "Annunciator" option without a page number specifies the first annunciator page in the following sequence:
The first annunciator page that contains an annunciator window that is in alarm (fast flash)
The first annunciator page that contains an annunciator window that is in ringback. Ringback is a "return alert."
Visual and audible signals are given when conditions return to normal, then the sequence returns to normal by
pushing the RESET button.
The first annunciator page that contains an annunciator window that is in abnormal state
Annunciator page 1
The Tabular option displays a configured actual values/metering page.
The Targets option displays error messages, such as wrong transceiver, similar to event record entries.

5.3.4 Clear relay records

SETTINGS  PRODUCT SETUP  CLEAR RELAY RECORDS
 CLEAR RELAY
 RECORDS
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
Figure 5-12: Configurable navigation editor
CLEAR USER REPORTS:
Off
Range: FlexLogic operand
PRODUCT SETUP
5
5-39