GE C70 Instruction Manual page 447

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
VOLTAGE DIF 1 STG 1 PKP DELAY
each of the 12 comparators (four stages in three phases) uses an individual timer, but settings for these timers are
controlled individually per each stage, not per phase. The timers use a common drop-out time delay specified by the next
setting.
— Controls a drop out delay for the operate FlexLogic operands. Note that individual stages apply
VOLTAGE DIF 1 DPO DELAY
individually configurable pickup delays, but use this common drop out delay.
to
VOLT DIF 1 BLK STG 1
VOLT DIF 1 BLK STG 4
required. At minimum this function shall be blocked when the bank is offline, or else it operates unnecessarily. Either
breaker position or undercurrent indication via any available instantaneous function, or a combination, can be used for
blocking. Also consider the VT fuse fail condition from both the bus and tap VT. When unblocked, the function becomes
operational after five cycles of intentional delay.
5.7.8.8 Bank phase overvoltage (ANSI 59B, IEC PTOV)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  VOLTAGE ELEMENTS  BANK OVERVOLTAGE 
BANK OVERVOLTAGE 1(3)
 BANK OVERVOLTAGE 1
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
— Specifies the pickup time delay, individually per each stage of alarming/tripping. Note that
— These inputs are used to block the function on a per stage basis when
Figure 5-129: Voltage differential logic
BANK OV 1
FUNCTION: Disabled
BANK OV 1 BUS
SOURCE: SRC 1
BANK OV 1 NTRL
SOURCE: SRC 1
GROUPED ELEMENTS
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
5
5-243