GE C70 Instruction Manual page 444

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

GROUPED ELEMENTS
5.7.8.7 Bank voltage differential (ANSI 87V, IEC PDIF)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  VOLTAGE ELEMENTS  VOLTAGE DIFFERENTIAL 1(3)
 VOLTAGE
 DIFFERENTIAL 1
5
5-240
Figure 5-127: Auxiliary overvoltage logic
VOLTAGE DIF 1
FUNCTION: Disabled
VOLTAGE DIF 1 BUS
SOURCE: SRC 1
VOLTAGE DIF 1 TAP
SOURCE: SRC 1
VOLTAGE DIF 1 BANK
GROUND: Grounded
VOLTAGE DIF 1 MATCH
FACTOR A: 2.0000
VOLTAGE DIF 1 MATCH
FACTOR B: 2.0000
VOLTAGE DIF 1 MATCH
FACTOR C: 2.0000
VOLTAGE DIF 1 STG 1A
PICKUP: 0.010 pu
VOLTAGE DIF 1 STG 2A
PICKUP: 0.020 pu
VOLTAGE DIF 1 STG 3A
PICKUP: 0.030 pu
VOLTAGE DIF 1 STG 4A
PICKUP: 0.040 pu
VOLTAGE DIF 1 STG 1B
PICKUP: 0.010 pu
VOLTAGE DIF 1 STG 2B
PICKUP: 0.020 pu
VOLTAGE DIF 1 STG 3B
PICKUP: 0.030 pu
VOLTAGE DIF 1 STG 4B
PICKUP: 0.040 pu
VOLTAGE DIF 1 STG 1C
PICKUP: 0.010 pu
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: Grounded, Ungrounded
Range: 0.5000 to 2000.0000 in steps of 0.0001
Range: 0.5000 to 2000.0000 in steps of 0.0001
Range: 0.5000 to 2000.0000 in steps of 0.0001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents