CHAPTER 2: PRODUCT DESCRIPTION
2.5.15 Approvals
APPROVALS
Compliance
Applicable council directive
CE
Low voltage directive
EMC directive
C-UL-US
---
2.5.16 Maintenance
MOUNTING
Attach mounting brackets using 20 inch-pounds (±2 inch-pounds) of torque.
CLEANING
Normally, cleaning is not required. When dust has accumulated on the front panel display, wipe with a dry cloth.
To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized
state once per year, for one hour continuously.
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
According to
EN 60255-5
EN 60255-26 / EN 50263
EN 61000-6-5
UL 508
UL 1053
C22.2 No. 14
SPECIFICATIONS
2
2-35