Eaton 93PM UPS 30–200 kVA
5.4.1
battery option
If you choose to order a multi-modular Eaton 93PM UPS (up to 200 kVA) with a
separate battery option, the UPS external battery connections require installing
a separate battery for each UPM. Figure
terminals in 93PM UPS with separate battery option.
Figure 21. Separate battery option battery terminals for 93PM 100 kW and 150 kW,
respectively
93PM 100 kW
1
Battery + for UPM 2
2
Battery + for UPM 1
3
Battery - for UPM 2
4
Battery - for UPM 1
©
Eaton Corporation plc 2017. All rights reserved.
Installing the battery system for 93PM UPS with separate
21
and Figure
93PM 150 kW
5
Battery + for UPM 3
6
Battery + for UPM 2
7
Battery + for UPM 1
8
Battery - for UPM 3
9
Battery - for UPM 2
10
Battery - for UPM 1
Revision: 005
Document ID: P-164000249
User's and installation guide
22