GE Multilin 745 Communications Manual page 91

Transformer protection system
Table of Contents

Advertisement

CHAPTER 2: MODBUS PROTOCOL
745 TRANSFORMER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
F52: Logic flags (16-bit bitmask)
Bitmask
Logic flag
–––– –––– –––– –––x
Pickup flag (0 = not picked up, 1 = picked up)
–––– –––– –––– ––x–
Operated flag (0 = not operated, 1 = operated)
–––– –––– –––– –x––
Latched flag (0 = not latched, 1 = latched)
–––– –––– –––– x–––
Self-test flag (0 = no error, 1 = error)
–––– –––– –––x ––––
Not used
–––– –––– ––x– ––––
Not used
–––– –––– –x–– ––––
Not used
–––– –––– x––– ––––
Not used
–––– –––x –––– ––––
Phase A flag (0 = no fault, 1 = fault)
–––– ––x– –––– ––––
Phase B flag (0 = no fault, 1 = fault)
–––– –x–– –––– ––––
Phase C flag (0 = no fault, 1 = fault)
–––– x––– –––– ––––
Ground flag (0 = no fault, 1 = fault)
F53: Unsigned value, 3 decimal places (16 bits)
Example: 1.234 stored as 1234
F54: Force LED state (16-bit bitmask)
Bitmask
LED state
–––– –––– –––– –––1
LED #1 on (top)
–––– –––– –––– ––1–
LED #2 on
–––– –––– –––– –1––
LED #3 on
–––– –––– –––– 1–––
LED #4 on
–––– –––– –––1 ––––
LED #5 on
–––– –––– ––1– ––––
LED #6 on
–––– –––– –1–– ––––
LED #7 on
–––– –––– 1––– ––––
LED #8 on (bottom)
F55: Front panel keypress (16-bit enumeration)
Value
Key
0
"0"
1
"1"
2
"2"
3
"3"
4
"4"
5
"5"
6
"6"
7
"7"
Value
Key
8
"8"
9
"9"
10
Decimal
11
Message up
12
Message down
13
Message left
14
Message right
15
Value up
MODBUS PROTOCOL
Value
Key
16
Enter
17
Reset
18
Menu
19
Escape
20
Value down
21
Help
2–85