GE Multilin 745 Communications Manual page 95

Transformer protection system
Table of Contents

Advertisement

CHAPTER 2: MODBUS PROTOCOL
745 TRANSFORMER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
F73: Parity (16-bit enumeration)
Value
Parity
0
None
1
Odd
2
Even
F74: Edit setpoint group (16-bit enumeration)
Value
Setpoint group
0
Group 1
1
Group 2
2
Group 3
2
Group 4
2
Active group
F75: Virtual input programmed state (16-bit enumeration)
Value
State
0
Open
1
Closed
F76: FlexLogic™ equation error (16-bit enumeration)
Value
Error
0
None
1
Output relay 1
2
Output relay 2
3
Output relay 3
4
Output relay 4
5
Output relay 5
6
Output relay 6
7
Output relay 7
F77: Bad transformer settings error (16-bit enumeration)
Value
Error
0
None
1
W1-W2 ratio mismatch
2
W2-W3 ratio mismatch
3
Load loss
4
Winding 1 eddy current loss
F78: Unsigned value, auto-ranging based on winding 1 phase CT primary value (16 bits)
For winding 1 phase CT primary ≤ 2 A, F78 is an unsigned value with three decimal places.
For example, 1.234 is stored as 1234.
For 2 A < winding 1 phase CT primary ≤ 20 A, F78 is an unsigned value with two decimal
places. For example, 12.34 is stored as 1234.
For 20 A < winding 1 phase CT primary ≤ 200 A, F78 is an unsigned value with one decimal
place. For example, 123.4 is stored as 1234.
For 200 A < winding 1 phase CT primary ≤ 2000 A, F78 is a standard unsigned value. For
example, 1234 is stored as 1234.
For winding 1 phase CT primary > 2000 A, F78 is a standard unsigned value scaled by 10.
For example, 12340 is stored as 1234.
Value
Error
8
Output relay 8
9
Trigger trace memory
10
Virtual output 1
11
Virtual output 2
12
Virtual output 3
13
Virtual output 4
14
Virtual output 5
Value
Error
5
Winding 2 eddy current loss
6
Winding 3 eddy current loss
7
Winding 1 rated load
8
Winding 2 rated load
9
Winding 3 rated load
MODBUS PROTOCOL
2–89