GE Multilin 745 Communications Manual page 65

Transformer protection system
Table of Contents

Advertisement

CHAPTER 2: MODBUS PROTOCOL
Table 2–4: 745 memory map (Sheet 47 of 56)
Addr
Description
21CF
Reserved
Winding 2 ground instantaneous overcurrent 2
21D0
Winding 2 ground instantaneous overcurrent 2 function
21D1
Winding 2 ground instantaneous overcurrent 2 target
21D2
Winding 2 ground instantaneous overcurrent 2 pickup
21D3
Winding 2 ground instantaneous overcurrent 2 delay
21D4
Winding 2 ground instantaneous overcurrent 2 block
21D5
Winding 2 ground instantaneous overcurrent 2 relays
21D6
Reserved
21DF
Reserved
Winding 3 ground instantaneous overcurrent 2
21E0
Winding 3 ground instantaneous overcurrent 2 function
21E1
Winding 3 ground instantaneous overcurrent 2 target
21E2
Winding 3 ground instantaneous overcurrent 2 pickup
21E3
Winding 3 ground instantaneous overcurrent 2 delay
21E4
Winding 3 ground instantaneous overcurrent 2 block
21E5
Winding 3 ground instantaneous overcurrent 2 relays
21E6
Reserved
21EF
Reserved
Winding 1 restricted ground fault
21F0
Winding 1 restricted ground fault function
21F1
Winding 1 restricted ground fault target
21F2
Winding 1 restricted ground fault pickup
21F3
Winding 1 restricted ground fault slope
21F4
Winding 1 restricted ground fault delay
21F5
Winding 1 restricted ground fault block
21F6
Winding 1 restricted ground fault relays
21F7
Reserved
21FF
Reserved
Winding 2 restricted ground fault
2200
Winding 2 restricted ground fault function
2201
Winding 2 restricted ground fault target
2202
Winding 2 restricted ground fault pickup
2203
Winding 2 restricted ground fault slope
2204
Winding 2 restricted ground fault delay
2205
Winding 2 restricted ground fault block
2206
Winding 2 restricted ground fault relays
2207
Reserved
220F
Reserved
Winding 3 restricted ground fault
2210
Winding 3 restricted ground fault function
2211
Winding 3 restricted ground fault target
745 TRANSFORMER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
Range
Step
---
---
---
---
0.05 to 20.00
0.01
0 to 60000
1
---
---
1 to 8
---
---
---
---
---
0.05 to 20.00
0.01
0 to 60000
1
---
---
1 to 8
---
---
---
---
---
0.02 to 20.00
0.01
0 to 100
1
0.00 to 600.00
0.01
---
---
1 to 8
---
---
---
---
---
0.02 to 20.00
0.01
0 to 100
1
0.00 to 600.00
0.01
---
---
1 to 8
---
---
---
---
---
MODBUS PROTOCOL
Units
Format
Default
---
F30
0 = Disabled
---
F46
1 = Latched
× CT
F3
1000=10.00xCT
ms
F1
0 ms
---
F87
0 = Disabled
---
F153
None
---
F30
0 = Disabled
---
F46
1 = Latched
× CT
F3
1000=10.00xCT
ms
F1
0 ms
---
F87
0 = Disabled
---
F153
None
---
F30
0 = Disabled
---
F46
1 = Latched
× CT
F3
8 = 0.08 × CT
%
F1
10%
s
F3
10 = 0.10 s
---
F87
0 = Disabled
---
F153
None
---
F30
0 = Disabled
---
F46
1 = Latched
× CT
F3
8 = 0.08 × CT
%
F1
10%
s
F3
10 = 0.10 s
---
F87
0 = Disabled
---
F153
None
---
F30
0 = Disabled
---
F46
1 = Latched
2–59