GE Multilin 745 Communications Manual page 40

Transformer protection system
Table of Contents

Advertisement

MODBUS PROTOCOL
Table 2–4: 745 memory map (Sheet 22 of 56)
Addr
Description
0857
Event XX winding 3 ground current magnitude
0858
Event XX winding 3 ground current angle
0859
Event XX winding 3 phase A 2nd harmonic
085A
Event XX winding 3 phase B 2nd harmonic
085B
Event XX winding 3 phase C 2nd harmonic
085C
Event XX winding 3 phase A 5th harmonic
085D
Event XX winding 3 phase B 5th harmonic
085E
Event XX winding 3 phase C 5th harmonic
085F
Event XX phase A differential current
0860
Event XX phase B differential current
0861
Event XX phase C differential current
0862
Event XX phase A restraint current
0863
Event XX phase B restraint current
0864
Event XX phase C restraint current
0865
Event XX system frequency
0866
Event XX frequency decay rate
0867
Event XX tap changer position
0868
Event XX volts-per-hertz
0869
Event XX ambient temperature
086A
Event XX analog input
086B
Reserved
086C
Reserved
086F
Reserved
Communications actual values
0870
CoBox serial number
0884
MAC address
0898
CoBox firmware version
08AC
Ethernet status
08AD
Reserved
08AE
Reserved
0FFF
Reserved
Common setpoints (addresses 1000 to 1FFF, read/write)
745 setup
1000
745 setpoints
1001
Encrypted passcode (4 registers, read only)
Note: From version 5.23 onward, relay
response to read request is 00000000.
1005
Reserved
1006
Flash message time
1007
Default message timeout
1008
Reserved
1009
Slave address
100A
COM1 baud rate
100B
COM1 parity
100C
COM1 communication hardware
100D
COM2 baud rate
2–34
Range
Step
---
---
0 to 359
1
0.0 to 99.9
0.1
0.0 to 99.9
0.1
0.0 to 99.9
0.1
0.0 to 99.9
0.1
0.0 to 99.9
0.1
0.0 to 99.9
0.1
0.00 to 655.35
0.01
0.00 to 655.35
0.01
0.00 to 655.35
0.01
0.00 to 655.35
0.01
0.00 to 655.35
0.01
0.00 to 655.35
0.01
0.00 to 99.99
0.01
–9.99 to 9.99
0.01
1 to 50
1
0.00 to 4.00
0.01
–51 to 251
1
0 to 65000
1
<Units>
---
---
---
---
---
---
---
---
---
---
---
---
0.5 to 10.0
0.5
10 to 900
1
1 to 254
1
---
---
---
---
---
---
---
---
745 TRANSFORMER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
CHAPTER 2: MODBUS PROTOCOL
Units
Format
Default
A
F83
0 A
° Lag
F1
0° Lag
% ƒo
F2
0% ƒo
% ƒo
F2
0% ƒo
% ƒo
F2
0% ƒo
% ƒo
F2
0% ƒo
% ƒo
F2
0% ƒo
% ƒo
F2
0% ƒo
× CT
0.00 × CT
F3
× CT
F3
0.00 × CT
× CT
F3
0.00 × CT
× CT
F3
0.00 × CT
× CT
F3
0.00 × CT
× CT
0.00 × CT
F3
Hz
F3
0.00 Hz
Hz/s
F6
0.00 Hz/s
---
F1
0 = n/a
V/Hz
F3
0.00 V/Hz
°C
F4
0 °C
F1
0 <Units>
---
F22
Unknown
---
F22
Unknown
---
F22
Unknown
---
F152
---
---
F29
0 = Not Prog'd
---
F33
00000000
s
F2
40 = 4.0 s
s
F1
300 s
---
F1
254
---
F31
5 = 19200 Bd
---
F73
0 = None
---
F17
0 = RS485
---
F31
5 = 19200 Bd

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents