GE Multilin 745 Communications Manual page 64

Transformer protection system
Table of Contents

Advertisement

MODBUS PROTOCOL
Table 2-4: 745 memory map (Sheet 46 of 56)
Addr
Description
2182
Winding 3 ground time overcurrent pickup
2183
Winding 3 ground time overcurrent shape
2184
Winding 3 ground time overcurrent multiplier
2185
Winding 3 ground time overcurrent reset
2186
Winding 3 ground time overcurrent block
2187
Winding 3 ground time overcurrent relays
2188
Reserved
218F
Reserved
Winding 1 ground instantaneous overcurrent 1
2190
Winding 1 ground instantaneous overcurrent 1 function
2191
Winding 1 ground instantaneous overcurrent 1 target
2192
Winding 1 ground instantaneous overcurrent 1 pickup
2193
Winding 1 ground instantaneous overcurrent 1 delay
2194
Winding 1 ground instantaneous overcurrent 1 block
2195
Winding 1 ground instantaneous overcurrent 1 relays
2196
Reserved
219F
Reserved
Winding 2 ground instantaneous overcurrent 1
21A0
Winding 2 ground instantaneous overcurrent 1 function
21A1
Winding 2 ground instantaneous overcurrent 1 target
21A2
Winding 2 ground instantaneous overcurrent 1 pickup
21A3
Winding 2 ground instantaneous overcurrent 1 delay
21A4
Winding 2 ground instantaneous overcurrent 1 block
21A5
Winding 2 ground instantaneous overcurrent 1 relays
21A6
Reserved
21AF
Reserved
Winding 3 ground instantaneous overcurrent 1
21B0
Winding 3 ground instantaneous overcurrent 1 function
21B1
Winding 3 ground instantaneous overcurrent 1 target
21B2
Winding 3 ground instantaneous overcurrent 1 pickup
21B3
Winding 3 ground instantaneous overcurrent 1 delay
21B4
Winding 3 ground instantaneous overcurrent 1 block
21B5
Winding 3 ground instantaneous overcurrent 1 relays
21B6
Reserved
21BF
Reserved
Winding 1 ground instantaneous overcurrent 2
21C0
Winding 1 ground instantaneous overcurrent 2 function
21C1
Winding 1 ground instantaneous overcurrent 2 target
21C2
Winding 1 ground instantaneous overcurrent 2 pickup
21C3
Winding 1 ground instantaneous overcurrent 2 delay
21C4
Winding 1 ground instantaneous overcurrent 2 block
21C5
Winding 1 ground instantaneous overcurrent 2 relays
21C6
Reserved
2-58
Range
Step
0.05 to 20.00
0.01
---
---
0.00 to 100.00
0.01
---
---
---
---
---
---
---
---
---
0.05 to 20.00
0.01
1
---
---
1 to 8
---
---
---
---
---
0.05 to 20.00
0.01
1
---
---
1 to 8
---
---
---
---
---
0.05 to 20.00
0.01
0 to 60000
1
---
---
---
---
---
---
---
0.05 to 20.00
0.01
0 to 60000
1
---
---
1 to 8
---
745 TRANSFORMER PROTECTION SYSTEM - COMMUNICATIONS GUIDE
CHAPTER 2: MODBUS PROTOCOL
Units
Format
Default
x CT
F3
85 = 0.85 x CT
---
0 = Ext Inverse
---
F3
100 = 1.00
---
1 = Linear
---
0 = Disabled
---
None
---
0 = Disabled
---
1 = Latched
1000=10.00xCT
0 ms
---
F87
0 = Disabled
---
F153
None
---
F30
0 = Disabled
---
F46
1 = Latched
x CT
F3
1000=10.00xCT
0 ms
---
F87
0 = Disabled
---
F153
None
---
F30
0 = Disabled
---
F46
1 = Latched
1000=10.00xCT
ms
F1
0 ms
---
0 = Disabled
---
None
---
0 = Disabled
---
1 = Latched
x CT
F3
1000=10.00xCT
ms
F1
0 ms
---
F87
0 = Disabled
---
F153
None