CHAPTER 2: MODBUS PROTOCOL
Table 2–4: 745 memory map (Sheet 43 of 56)
Addr
Description
20B1
Winding 2 phase instantaneous overcurrent 2 target
20B2
Winding 2 phase instantaneous overcurrent 2 pickup
20B3
Winding 2 phase instantaneous overcurrent 2 delay
20B4
Winding 2 phase instantaneous overcurrent 2 block
20B5
Winding 2 phase instantaneous overcurrent 2 relays
20B6
Reserved
20BF
Reserved
Winding 3 phase instantaneous overcurrent 2
20C0
Winding 3 phase instantaneous overcurrent 2 function
20C1
Winding 3 phase instantaneous overcurrent 2 target
20C2
Winding 3 phase instantaneous overcurrent 2 pickup
20C3
Winding 3 phase instantaneous overcurrent 2 delay
20C4
Winding 3 phase instantaneous overcurrent 2 block
20C5
Winding 3 phase instantaneous overcurrent 2 relays
20C6
Reserved
20CF
Reserved
Winding 1 neutral time overcurrent
20D0
Winding 1 neutral time overcurrent function
20D1
Winding 1 neutral time overcurrent target
20D2
Winding 1 neutral time overcurrent pickup
20D3
Winding 1 neutral time overcurrent shape
20D4
Winding 1 neutral time overcurrent multiplier
20D5
Winding 1 neutral time overcurrent reset
20D6
Winding 1 neutral time overcurrent block
20D7
Winding 1 neutral time overcurrent relays
20D8
Reserved
20DF
Reserved
Winding 2 neutral time overcurrent
20E0
Winding 2 neutral time overcurrent function
20E1
Winding 2 neutral time overcurrent target
20E2
Winding 2 neutral time overcurrent pickup
20E3
Winding 2 neutral time overcurrent shape
20E4
Winding 2 neutral time overcurrent multiplier
20E5
Winding 2 neutral time overcurrent reset
20E6
Winding 2 neutral time overcurrent block
20E7
Winding 2 neutral time overcurrent relays
20E8
Reserved
20EF
Reserved
Winding 3 neutral time overcurrent
20F0
Winding 3 neutral time overcurrent function
20F1
Winding 3 neutral time overcurrent target
20F2
Winding 3 neutral time overcurrent pickup
20F3
Winding 3 neutral time overcurrent shape
745 TRANSFORMER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
Range
Step
---
---
0.05 to 20.00
0.01
0 to 60000
1
---
---
1 to 8
---
---
---
---
---
0.05 to 20.00
0.01
0 to 60000
1
---
---
1 to 8
---
---
---
---
---
0.05 to 20.00
0.01
---
---
0.00 to 100.00
0.01
---
---
---
---
1 to 8
---
---
---
---
---
0.05 to 20.00
0.01
---
---
0.00 to 100.00
0.01
---
---
---
---
1 to 8
---
---
---
---
---
0.05 to 20.00
0.01
---
---
MODBUS PROTOCOL
Units
Format
Default
---
F46
1 = Latched
x CT
F3
1000=10.00xCT
ms
F1
0 ms
---
F87
0 = Disabled
---
F153
None
---
F30
1 = Enabled
---
F46
1 = Latched
x CT
F3
1000=10.00xCT
ms
F1
0 ms
---
F87
0 = Disabled
---
F153
None
---
F30
1 = Enabled
---
F46
1 = Latched
x CT
F3
85 = 0.85 x CT
---
F36
0 = Ext Inverse
---
F3
100 = 1.00
---
F68
1 = Linear
---
F87
0 = Disabled
---
F153
None
---
F30
0 = Disabled
---
F46
1 = Latched
x CT
F3
85 = 0.85 x CT
---
F36
0 = Ext Inverse
---
F3
100 = 1.00
---
F68
1 = Linear
---
F87
0 = Disabled
---
F153
None
---
F30
0 = Disabled
---
F46
1 = Latched
× CT
F3
85 = 0.85 × CT
---
F36
0 = Ext Inverse
2–55