Table 2–4: 745 memory map (Sheet 49 of 56)
Addr
Description
2282
Winding 1 negative-sequence inst. overcurrent pickup
2283
Winding 1 negative-sequence inst. overcurrent delay
2284
Winding 1 negative-sequence inst. overcurrent block
2285
Winding 1 negative-sequence inst. overcurrent relays
2286
Reserved
228F
Reserved
Winding 2 negative-sequence instantaneous overcurrent
2290
Winding 2 negative-sequence inst. overcurrent function
2291
Winding 2 negative-sequence inst. overcurrent target
2292
Winding 2 negative-sequence inst. overcurrent pickup
2293
Winding 2 negative-sequence inst. overcurrent delay
2294
Winding 2 negative-sequence inst. overcurrent block
2295
Winding 2 negative-sequence inst. overcurrent relays
2296
Reserved
229F
Reserved
Winding 3 negative-sequence instantaneous overcurrent
22A0
Winding 3 negative-sequence inst. overcurrent function
22A1
Winding 3 negative-sequence inst. overcurrent target
22A2
Winding 3 negative-sequence inst. overcurrent pickup
22A3
Winding 3 negative-sequence inst. overcurrent delay
22A4
Winding 3 negative-sequence inst. overcurrent block
22A5
Winding 3 negative-sequence inst. overcurrent relays
22A6
Reserved
22AF
Reserved
Underfrequency 1
22B0
Underfrequency 1 function
22B1
Underfrequency 1 target
22B2
Underfrequency 1 minimum operating current
22B3
Underfrequency 1 pickup
22B4
Underfrequency 1 delay
22B5
Underfrequency 1 block
22B6
Underfrequency 1 current sensing
22B7
Underfrequency 1 minimum operating voltage
22B8
Underfrequency 1 relays
22B9
Reserved
22BF
Reserved
Underfrequency 2
22C0
Underfrequency 2 function
22C1
Underfrequency 2 target
22C2
Underfrequency 2 minimum operating current
22C3
Underfrequency 2 pickup
22C4
Underfrequency 2 delay
22C5
Underfrequency 2 block
745 TRANSFORMER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
Range
Step
0.05 to 20.00
0.01
0 to 60000
1
---
---
1 to 8
---
---
---
---
---
0.05 to 20.00
0.01
0 to 60000
1
---
---
1 to 8
---
---
---
---
---
0.05 to 20.00
0.01
0 to 60000
1
---
---
1 to 8
---
---
---
---
---
0.05 to 1.00
0.01
45.00 to 59.99
0.01
0.00 to 600.00
0.01
---
---
---
---
0.10 to 0.99
0.01
1 to 8
---
---
---
---
---
0.05 to 1.00
0.01
45.00 to 59.99
0.01
0.00 to 600.00
0.01
---
---
MODBUS PROTOCOL
Units
Format
Default
× CT
F3
1000=10.00xCT
ms
F1
0 ms
---
F87
0 = Disabled
---
F153
None
---
F30
0 = Disabled
---
F46
1 = Latched
× CT
F3
1000=10.00xCT
ms
F1
0 ms
---
F87
0 = Disabled
---
F153
None
---
F30
0 = Disabled
---
F46
1 = Latched
× CT
F3
1000=10.00xCT
ms
F1
0 ms
---
F87
0 = Disabled
---
F153
None
---
F30
0 = Disabled
---
F46
0 = Self-reset
× CT
F3
20 = 0.20 × CT
Hz
F3
5900 = 59.0 Hz
s
F3
100 = 1.00 s
---
F87
0 = Disabled
---
F30
1 = Enabled
× VT
F3
50 = 0.50 × VT
---
F153
None
---
F30
0 = Disabled
---
F46
1 = Latched
× CT
F3
20 = 0.20 × CT
Hz
F3
5880 = 58.8 Hz
s
F3
10 = 0.10 s
---
F87
0 = Disabled
2–61