CHAPTER 2: MODBUS PROTOCOL
745 TRANSFORMER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
F31: Baud rate (16-bit enumeration)
Value
Baud rate
0
300 baud
1
1200 baud
2
2400 baud
3
4800 baud
4
9600 baud
5
19200 baud
F32: Default message (32 bits)
Internally defined
F33: ASCII text characters (16 bits)
First block of eight bits: first ASCII character, 0 to 255 in steps of 1
Second block of eight bits: second ASCII character, 0 to 255 in steps of 1
Example: "AN" stored as 414Eh = 16718 decimal
F34: Relay energization state (16-bit enumeration)
Value
Relay state
0
De-energized
1
Energized
F35: Relay conditions (16-bit bitmask)
Bitmask
Description
–––– –––– –––– –––1
Active trip condition
–––– –––– –––– ––1–
Active alarm condition(s)
–––– –––– –––– –1––
Pickup condition
–––– –––– –––1 ––––
Phase A fault
–––– –––– ––1– ––––
Phase B fault
–––– –––– –1–– ––––
Phase C fault
–––– –––– 1––– ––––
Ground fault
F36: Overcurrent curve shape (16-bit enumeration)
Value
Curve shape
0
IEEE extremely inverse
1
IEEE very inverse
2
IEEE normally inverse
3
IEEE moderately inverse
4
Definite time
5
IEC curve A
6
IEC curve B
7
IEC curve C
F37: Rated winding temperature rise (16-bit enumeration)
Value
Temperature rise
0
55°C (oil)
1
65°C (oil)
2
80°C (dry)
3
115°C (dry)
4
150°C (dry)
Value
Curve shape
8
IEC short inverse
9
IAC extremely inverse
10
IAC very inverse
11
IAC inverse
12
IAC short inverse
13
FlexCurve™ A
14
FlexCurve™ B
15
FlexCurve™ C
MODBUS PROTOCOL
2–77