GE Multilin 745 Communications Manual page 71

Transformer protection system
Table of Contents

Advertisement

CHAPTER 2: MODBUS PROTOCOL
Table 2–4: 745 memory map (Sheet 53 of 56)
Addr
Description
Hottest- spot limit
2380
Hottest-spot limit function
2381
Hottest-spot limit target
2382
Hottest-spot limit pickup
2383
Hottest-spot limit delay
2384
Hottest-spot limit block
2385
Hottest-spot limit relays
2386
Reserved
238F
Reserved
Loss-of-life limit
2390
Loss-of-life limit function
2391
Loss-of-life limit target
2392
Loss-of-life limit pickup
2393
Loss-of-life limit block
2394
Loss-of-life limit relays
2395
Reserved
239F
Reserved
Analog input level 1
23A0
Analog input level 1 function
23A1
Analog input level 1 target
23A2
Analog input level 1 pickup
23A3
Analog input level 1 delay
23A4
Analog input level 1 block
23A5
Analog input level 1 relays
23A6
Reserved
23AF
Reserved
Analog input level 2
23B0
Analog input level 2 function
23B1
Analog input level 2 target
23B2
Analog input level 2 pickup
23B3
Analog input level 2 delay
23B4
Analog input level 2 block
23B5
Analog input level 2 relays
23B6
Reserved
23BF
Reserved
Winding 1 current demand
23C0
Winding 1 current demand function
23C1
Winding 1 current demand target
23C2
Winding 1 current demand pickup
23C3
Winding 1 current demand block
23C4
Winding 1 current demand relays
23C5
Reserved
745 TRANSFORMER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
Range
Step
Units
---
---
---
---
---
---
50 to 300
1
° C
0 to 60000
1
min
---
---
---
1 to 8
---
---
---
---
---
---
---
---
0 to 20000
1
hrs x 10
---
---
---
1 to 8
---
---
---
---
---
---
---
---
1 to 65000
1
<Units>
0 to 60000
1
---
---
---
1 to 8
---
---
---
---
---
---
---
---
1 to 65000
1
<Units>
0 to 60000
1
---
---
---
1 to 8
---
---
---
---
---
---
---
---
---
---
---
---
---
1 to 8
---
---
MODBUS PROTOCOL
Format
Default
F30
0 = Disabled
F46
0 = Self-reset
F1
150° C
F1
10 min
F87
0 = Disabled
F153
None
F30
0 = Disabled
F46
0 = Self-reset
F1
160000 hrs.
F87
0 = Disabled
F153
None
F30
0 = Disabled
F46
0 = Self-reset
F1
10 <Units>
s
F1
50 s
F87
0 = Disabled
F153
None
F30
0 = Disabled
F46
0 = Self-reset
F1
100 <Units>
s
F1
100 s
F87
0 = Disabled
F153
None
F30
0 = Disabled
F46
0 = Self-reset
A
F78
100 A
F87
0 = Disabled
F153
None
2–65