MODBUS PROTOCOL
Table 2–4: 745 memory map (Sheet 52 of 56)
Addr
Description
233F
Reserved
Winding 3 THD level
2340
Winding 3 THD level function
2341
Winding 3 THD level target
2342
Winding 3 THD level minimum operating current
2343
Winding 3 THD level pickup
2344
Winding 3 THD level delay
2345
Winding 3 THD level block
2346
Winding 3 THD level relays
2347
Reserved
↓
↓
234F
Reserved
Winding 1 harmonic derating
2350
Winding 1 harmonic derating function
2351
Winding 1 harmonic derating target
2352
Winding 1 harmonic derating minimum operating current
2353
Winding 1 harmonic derating pickup
2354
Winding 1 harmonic derating delay
2355
Winding 1 harmonic derating block
2356
Winding 1 harmonic derating relays
2357
Reserved
↓
↓
235F
Reserved
Winding 2 harmonic derating
2360
Winding 2 harmonic derating function
2361
Winding 2 harmonic derating target
2362
Winding 2 harmonic derating minimum operating current
2363
Winding 2 harmonic derating pickup
2364
Winding 2 harmonic derating delay
2365
Winding 2 harmonic derating block
2366
Winding 2 harmonic derating relays
2367
Reserved
↓
↓
236F
Reserved
Winding 3 harmonic derating
2370
Winding 3 harmonic derating function
2371
Winding 3 harmonic derating target
2372
Winding 3 harmonic derating minimum operating current
2373
Winding 3 harmonic derating pickup
2374
Winding 3 harmonic derating delay
2375
Winding 3 harmonic derating block
2376
Winding 3 harmonic derating relays
2377
Reserved
↓
↓
237F
Reserved
2–64
Range
Step
---
---
---
---
0.03 to 1.00
0.01
0.1 to 50.0
0.1
0 to 60000
1
---
---
1 to 8
---
↓
↓
---
---
---
---
0.03 to 1.00
0.01
0.01 to 0.98
0.01
0 to 60000
1
---
---
1 to 8
---
↓
↓
---
---
---
---
0.03 to 1.00
0.01
0.01 to 0.98
0.01
0 to 60000
1
---
---
1 to 8
---
↓
↓
---
---
---
---
0.03 to 1.00
0.01
0.01 to 0.98
0.01
0 to 60000
1
---
---
1 to 8
---
↓
↓
745 TRANSFORMER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
CHAPTER 2: MODBUS PROTOCOL
Units
Format
Default
---
F30
0 = Disabled
---
F46
0 = Self-reset
× CT
F3
10 = 0.10 × CT
% ƒo
F2
500 = 50.0%
s
F1
10 s
---
F87
0 = Disabled
---
F153
None
↓
↓
↓
---
F30
0 = Disabled
---
F46
0 = Self-reset
× CT
10 = 0.10 × CT
F3
---
F3
90 = 0.90
s
F1
10 s
---
F87
0 = Disabled
---
F153
None
↓
↓
↓
---
F30
0 = Disabled
---
F46
0 = Self-reset
× CT
F3
10 = 0.10 × CT
---
F3
90 = 0.90
s
F1
10 s
---
F87
0 = Disabled
---
F153
None
↓
↓
↓
---
F30
0 = Disabled
---
F46
0 = Self-reset
× CT
F3
10 = 0.10 × CT
---
F3
90 = 0.90
s
F1
10 s
---
F87
0 = Disabled
---
F153
None
↓
↓
↓