Table 2–4: 745 memory map (Sheet 25 of 56)
Addr
Description
10FF
Reserved
Transformer
1100
Nominal frequency
1101
Phase sequence
1102
Transformer type
1103
Rated winding temperature rise
1104
Type of cooling: oil immersed
1105
Load loss at rated load (2 registers)
1107
No-load loss
1108
Top oil rise over ambient (at rated load)
1109
Transformer thermal capacity
110A
Winding time constant: oil-immersed
110B
Type of cooling: dry
110C
Thermal time constant: dry
110D
Set initial accumulated loss of life
110E
Frequency tracking
110F
Reserved
1110
Reserved
111F
Reserved
Transformer winding 1
1120
Winding 1 nominal phase-to-phase voltage
1121
Winding 1 rated load
1122
Winding 1 phase CT primary
1123
Winding 1 ground CT primary
1124
Winding 1 series three-phase resistance
1125
Winding 1 Ground Input Selection
1126
Reserved
1127
Reserved
112F
Reserved
Transformer winding 2
1130
Winding 2 nominal phase-to-phase voltage
1131
Winding 2 rated load
1132
Winding 2 phase CT primary
1133
Winding 2 ground CT primary
1134
Winding 2 series three-phase resistance
1135
Winding 2 Ground Input Selection
1136
Reserved
1137
Reserved
113F
Reserved
Transformer winding 3
1140
Winding 3 nominal phase-to-phase voltage
1141
Winding 3 rated load
1142
Winding 3 phase CT primary
1143
Winding 3 ground CT primary
745 TRANSFORMER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
Range
Step
50 to 60
10
---
---
---
---
---
---
---
---
1 to 20000
1
0.1 to 2000
0.1
1 to 200
1
0.00 to 200.00
0.01
0.25 to 15.00
0.01
-
-
0.25 to 15.00
0.01
0 to 20000
1
---
---
1 to 20000
---
1 to 20000
---
1 to 50000
1
1 to 50000
1
0.001 to 50.000
0.001
None, G1/2, G2/3
---
1 to 20000
---
1 to 20000
---
1 to 50000
1
1 to 50000
1
0.001 to 50.000
0.001
None, G1/2, G2/3
---
1 to 20000
---
1 to 20000
---
1 to 50000
1
1 to 50000
1
MODBUS PROTOCOL
Units
Format
Default
Hz
F1
60 Hz
---
F27
0 = ABC
---
F28
3 = Y/d30°
---
F37
1 = 65°C (oil)
---
F39
0 = 0A
kW
F101
1250 kW
kW
F90
1250=125.0 kW
°C
F1
10°C
kWh/°C
F3
1.00 kWh/°C
minutes
F3
200 = 2.00 min
-
F100
0
minutes
F3
200 = 2.00 min
hrs x 10
F1
0 hours
---
F30
1 = Enabled
kV
F90
220.0 kV
MVA
F90
1000 = 100 MVA
:1 or :5 A
F1
500 A
:1 or :5 A
F1
500 A
ohms
F53
10700 = 10.7 Ω
---
F103

None

kV
F90
690 = 69.0 kV
MVA
F90
1000 = 100 MVA
:1 or :5 A
F1
1500 A
:1 or :5 A
F1
1500 A
ohms
F53
2100 = 2.100 Ω
---
F103
None
kV
F90
690 = 69.0 kV
MVA
F90
1000 = 100 MVA
:1 or :5 A
F1
1500 A
:1 or :5 A
F1
1500 A
2–37