RTD MAXIMUMS

RTD Maximums
NOTE:
NOTE
NOTE:
NOTE

Analog Inputs

FlexElements

6–20
Path:
Metering > RTD Maximums
The Temperature can be displayed in Celsius or Fahrenheit degrees. The selection is made
in Setpoints > Device > Installation > Temperature Display.
Reset RTD
Date/Time
Range: DD/MM/YY hh/mm/ss
Maximum RTD values can be cleared (reset) by setting the value of Setpoints > Records >
Clear Records > RTD Maximums to "ON". Executing this command loads -40°C as the initial
Maximum RTD value.
RTD 1(13)
Max
Range: -40 to 250°C (temperatures < -40°C are displayed as "Shorted" and temperatures >
250°C are displayed as "Open RTD")
RTD 1(13)
Max
Date/Time
Range: DD/MM/YY hh/mm/ss
Path:
Metering > Analog Inputs
Analog Ip 1 (4)
Range: -500000 to 500000 units in steps of 1
Path:
Metering > FlexElements
The operating signals for the FlexElements are displayed in pu values using the definitions
of the base units in the Definitions of the Base Unit for the FLEXELEMENT table. This table is
in the Setpoints>FlexLogic>FlexElements section.
FlexElement Operating Signals:
FlexEI 1 Op Signal
FlexEI 2 Op Signal
FlexEI 3 Op Signal
FlexEI 4 Op Signal
FlexEI 5 Op Signal
FlexEI 6 Op Signal
FlexEI 7 Op Signal
FlexEI 8 Op Signal
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: METERING