RTD MAXIMUMS

RTD Maximums
NOTE:
NOTE
NOTE:
NOTE
6–18
Path:
Metering > RTD Maximums
Metering\RTD Maximums
Item Name
Reset RTD Date/Time
RTD 1 Max
RTD 1 Max Date/Time
RTD 6 Max
RTD 6 Max Date/Time
RTD 7 Max
RTD 7 Max Date/Time
RTD 12 Max
RTD 12 Max Date/Time
RTD Max
The Temperature can be displayed in Celsius or Fahrenheit degrees. The selection is made
in Setpoints > Device > Front Panel > Display Properties > Temperature Display.
Reset RTD
Date/Time
Range: DD/MM/YY hh/mm/ss
Maximum RTD values can be cleared (reset) by setting the value of Setpoints > Records >
Clear Records > RTD Maximums to "YES". Executing this command loads -40°C as the initial
Maximum RTD value.
RTD 1(13)
Max
Range: -40 to 250°C (temperatures < -40°C are displayed as "Shorted" and temperatures >
250°C are displayed as "Open RTD")
RTD 1(13)
Max
Date/Time
Range: DD/MM/YY hh/mm/ss
Value
Unit
01/01/08 00:00:00
40
°C
01/01/08 00:00:00
40
°C
01/01/08 00:00:00
40
°C
01/01/08 00:00:00
40
°C
01/01/08 00:00:00
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: METERING