CHAPTER 4: SETPOINTS
..\Transformer\Winding 1
Item Name
Rated MVA
Nominal Ph Ph Voltage
Connection
Grounding
W 1
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Differential and Restraint Current Calculations
Two Winding Transformer
Differential currents are calculated as follows:
C
C
Id
= I
[w1] + I
[w2]
A
A
A
C
C
Id
= I
[w1] + I
[w2]
B
B
B
C
C
Id
= I
[w1] + I
[w2]
C
C
C
Restraint currents are calculated as follows:
C
Ir
= max {|I
[w1]| , |I
A
A
C
Ir
= max {|I
[w1]| , |I
B
B
C
Ir
= max {|I
[w1]| , |I
C
C
where Id
, Id
and Id
are the phase differential currents, and Ir
A
B
C
restraint currents.
EXAMPLE
Consider a typical Wye/Delta power transformer with the following data:
Value
5.000
13.800
Wye
Within Zone
Winding 1: (K2) = 500/5 CT ratio
Winding 2: (K1) = 1500/5 CT ratio
Transformer is 50% loaded
Magnitude Compensation
Based on 50% loading the winding currents are calculated as follows:
Winding 1 load current: I
Winding 2 load current: I
Since Winding 1 is always magnitude compensation reference, the currents from winding
1 , are scaled only to be presented in times Winding 1 CT.
M
= 1 , - magnitude compensation factor for winding 1 - REFERENCE
W1
Winding 1 currents = (M
Magnitude compensation for winding 2 currents:
M
= (CT
.V
)/ (CT
W2
W2
W2
factor for Winding 2 currents
Winding 2 currents = (M
To check that the measured currents from both windings will sum-up to zero after
applying magnitude compensation, one can perform the following simple calculations:
C
[w2]|}
A
C
[w2]|}
B
C
[w2]|}
C
..\Transformer\Winding 2
Unit
Item Name
MVA
Rated MVA
kV
Nominal Ph Ph Voltage
Connection
Angle With Respect To W1
Grounding
W 2
(W1) = 2.5MVA/(√3 * 13.8kV) = 104.5 Amps
load
(W2) = 2.5MVA/(√3 * 4.16kV) = 347 Amps
load
*I
(W
))/CT
= 104.5/500 = 0.209 x CT
W1
load
1
W1
.V
) = (1500*4.16)/(500*13.8) = 0.9043, -magnitude comp.
W1
W1
* I
(W
))/CT
= (0.9043*347)/1500 = 0.209 x CT
W2
load
2
W2
SYSTEM
, Ir
, and Ir
are the phase
A
B
C
Value
Unit
5.000
MVA
4.160
kV
Delta
30 ° lag
Not Within Zone
W1
W2
4–83