GE 889 Instruction Manual page 478

Generator protection system
Hide thumbs Also See for 889:
Table of Contents

Advertisement

CONTROL
FASTPATH:
4–348
BKR LOCAL CLOSE
Range: Off, Pushbutton 1 ON,.......Pushbutton 10 ON, Contact Input X
Default: Pushbutton 2 ON
This setpoint is active, when Local Mode is activated. The breaker close command can
be initiated by the selected faceplate pushbutton.
SW LOCAL OPEN
Range: Off, Pushbutton 1 ON,.......Pushbutton 10 ON, Contact Input X
Default: Pushbutton 1 ON
This setpoint is active, when Local Mode is activated. The switch open command can be
initiated by the programmed faceplate pushbutton. The setpoint appears in the Local
Control Mode menu only when advanced SLD is selected when ordering the relay.
SW LOCAL CLOSE
Range: Off, Pushbutton 1 ON,.......Pushbutton 10 ON, Contact Input X
Default: Pushbutton 2 ON
This setpoint is active, when Local Mode is activated. The switch close command can be
initiated by the programmed faceplate pushbutton. The setpoint appears in the Local
Control Mode menu only when advanced SLD is selected when ordering the relay.
TAGGING
Range: Enabled, Disabled
Default: Enabled
When enabled, tagging control is enabled and the TAG key is displayed on the front
panel interface. When a breaker or a switch is tagged both the local and remote control
of the device is inhibited.
Tagging is applied only from the TAG key and is mostly used for maintenance purposes,
and in general when either the open or close control must be inhibited. The tagging cannot
be bypassed and can only be disabled (untagged) by pressing the TAG key again.
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: SETPOINTS