CHAPTER 4: SETPOINTS
REV Operating
Region
-ECA line
-Isg line
VCG
NOTE:
NOTE
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 4-70: Sensitive Ground Directional Voltage-polarized Characteristics
REV LA
line
LA
LA
REV LA
line
Path:
Setpoints > Protection > Group 1(6) > Current > Sens Ground Directional OC 1(X)
FUNCTION
Range: Disabled, Enabled
Default: Disabled
POLARIZING MODE
Range: Voltage, Current, Dual
Default: Voltage
It is not recommended to use this function in the case of 50:0.025A CT input. If this is
applied consider Isg phasor metering errors in magnitude and angle in the settings.
This setting selects the polarizing mode for the directional unit.
If Voltage polarizing mode is selected, the element uses the zero-sequence voltage
angle for polarization. The user can select either the zero-sequence voltage V_0,
calculated from the phase voltages, or the zero-sequence voltage supplied externally
as the auxiliary voltage V_X.
-3V_0 line
FWD LA
line
VAG
(reference)
LA
ECA
FWD LA
line
3V_0 line
PROTECTION
FWD Operating
Region
Isg line
ECA line
LA
VBG
827805Y1.CDR
4–199