5.9 TRANSDUCER INPUTS AND OUTPUTS


PATH: SETTINGS
TRANSDUCER I/O
 RTD INPUT H1
5
The RTD inputs convert values of input resistance into temperature for further operations. These channels are intended to
be connected to any of the RTD types in common use. Specific hardware details are contained in chapter 3.
RTD input channels are arranged in a manner similar to CT and VT channels. The user configures individual channels with
the settings shown here.
The channels are arranged in sub-modules of two channels, numbered from 1 through 8 from top to bottom. On power-up,
the relay will automatically generate configuration settings for every channel, based on the order code, in the same general
manner that is used for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclu-
sive, which is used as the channel number. The relay generates an actual value for each available input channel.
Settings are automatically generated for every channel available in the specific relay as shown above for the first channel of
a type 5C transducer module installed in the first available slot.
RTD INPUT H1 FUNCTION: The function of the channel may be either "Enabled" or "Disabled". If set to "Disabled",
there will not be an actual value created for the channel.
RTD INPUT H1 ID: An alphanumeric ID is assigned to the channel. This ID will be included in the channel actual val-
ues. It is also used to reference the channel as the input parameter to features designed to measure this type of
parameter.
5-236


RTD INPUTS

RTD INPUT H1
FUNCTION: Disabled
RTD INPUT H1 ID:
MESSAGE
RTD Ip 1
RTD INPUT H1 TYPE:
MESSAGE
100Ω Nickel
RTD INPUT H1
MESSAGE
APPLICATION: Bearing
RTD INPUT H1 ALARM
MESSAGE
TEMPERATURE: 130°C
RTD INPUT H1 ALARM
MESSAGE
PKP DELAY: 0.00 s
RTD INPUT H1 TRIP
MESSAGE
TEMPERATURE: 130°C
RTD INPUT H1 TRIP
MESSAGE
PKP DELAY: 0.00 s
RTD INPUT H1 TRIP
MESSAGE
RST DELAY: 0.00 s
RTD INPUT H1 TRIP
MESSAGE
VOTING: None
RTD INPUT H1 OPEN:
MESSAGE
None
RTD INPUT H1 BLOCK:
MESSAGE
Off
RTD INPUT H1 TARGET:
MESSAGE
Self-reset
RTD INPUT H1 EVENTS:
MESSAGE
Disabled
M60 Motor Protection System
RTD INPUT H1(W8)
Range: Disabled, Enabled
Range: Up to 20 alphanumeric characters
Range: 100
120
Range: None, Stator, Bearing, Ambient, Group 1,
Group 2
Range: 1 to 249°C in steps of 1
Range: 0.00 to 600.00 s in steps of 0.01
Range: 1 to 249°C in steps of 1
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: None, Group, RTD Inp H1, RTD Inp H2,...,
RTD Inp W8
Range: None, Alarm, Block
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5 SETTINGS
5.9.2 RTD INPUTS
Ω
Ω
Ω
Nickel, 10
Copper, 100
Platinum,
Ω
Nickel