MONITORING
4–280
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
The thermal overload protection can be blocked by any asserted FlexLogic™ operand.
RELAYS
Range: Do Not Operate, Operate
Default: Do Not Operate
Any assignable output relay can be selected to operate upon Thermal Protection
operation.
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset