GE 889 Instruction Manual page 505

Generator protection system
Hide thumbs Also See for 889:
Table of Contents

Advertisement

CHAPTER 4: SETPOINTS
ELEMENT
OPERANDS
Breaker Health
BKR 1 Hlth PKP
BKR 1 Hlth Trip PKP
BKR 1 Hlth Cls PKP
BKR 1 Hlth Chg PKP
BKR 1 Arc PKP A
BKR 1 Arc PKP B
BKR 1 Arc PKP C
BKR 1 Engy PKP A
BKR 1 Engy PKP B
BKR 1 Engy PKP C
BKR 1 Hlth OP Fail
BKR 1 Arc Fail
BKR 1 Charge Fail
Close Circuit Monitoring
Cls Coil Mon 1 PKP
Cls Coil Mon 1 OP
Contact Inputs
CI # On
CI # Off
Critical Failure Relay
Critical Fail OP
Demand
Current Dmd PKP
Current Dmd PKP A
Current Dmd PKP B
Current Dmd PKP C
RealPwr Dmd PKP
ReactvPwr Dmd PKP
ApprntPwr Dmd PKP
Digital Counters
Counter 1 HI
Counter 1 EQL
Counter 1 LO
Counter 1 at Limit
Counter 2 to Counter 16
Frequency Rate-Of-
FreqRate1 PKP
Change
FreqRate1 OP
FreqRate1 Up PKP
FreqRate1 Up OP
FreqRate1 Dwn PKP
FreqRate1 Dwn OP
Directional Power
DirPwr 1 Stg1 PKP
DirPwr 1 Stg2 PKP
DirPwr 1 PKP
DirPwr 1 Stg1 OP
DirPwr 1 Stg2 OP
DirPwr 1 OP
DirPwr 2
Field Breaker Discrepancy Fld Bkr Discr PKP
Fld Bkr Discr OP
FlexElements
FlexEl 1 PKP
FlexEl 1 OP
FlexEl 2 to 8
Freq. OOB Accum
Freq OOB 1(7) Accum PKP
Freq OOB 1(7) Accum OP
Front Panel, Targets, LEDs,
Any Target
Pushbuttons
^^ PB[X] On
^^ PB[X] Off
Testing On
Testing Off
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
EVENT DESCRIPTION
Breaker health has picked up
Trip time of breaker health has picked up
Close time of breaker health has picked up
Spring charge time of breaker health has picked up
Arc time of phase A of breaker health has picked up
Arc time of phase B of breaker health has picked up
Arc time of phase C of breaker health has picked up
Arc energy of phase A of breaker health has picked up
Arc energy of phase B of breaker health has picked up
Arc energy of phase C of breaker health has picked up
Breaker trip or close operation has failed
Breaker arc time has failed
Spring charge time has failed
Close Coil 1 Monitoring element has picked up.
Close Coil 1 Monitoring element has operated for an amount of time
greater than the Close Circuit Monitor Pick-up Delay Time.
# – any contact input number
The critical failure relay operated
At least one phase from current demand element has picked up
Phase A from current demand element has picked up
Phase B from current demand element has picked up
Phase C from current demand element has picked up
Real power demand has picked up
Reactive power demand has picked up
Apparent power demand has picked up
Digital counter 1 output is 'more than' comparison value
Digital counter 1 output is 'equal to' comparison value
Digital counter 1 output is 'less than' comparison value
Digital counter 1 reached limit
Same set of operands as for Counter 1
The frequency rate of change 1 element has picked up
The frequency rate of change 1 element has operated
The frequency rate of change 1 element has picked up on raising
frequency
The frequency rate of change 1 element has operated on raising
frequency
The frequency rate of change 1 element has picked up on lowering
frequency
The frequency rate of change 1 element has operated on lowering
frequency
Stage 1 of the directional power element 1 has picked up
Stage 2 of the directional power element 1 has picked up
The directional power element has picked up
Stage 1 of the directional power element 1 has operated
Stage 2 of the directional power element 1 has operated
The directional power element has operated
The same set of operands per DirPwr 1
Pickup when the generator is online and field breaker is open.
Operate when the field breaker discrepancy exceeds the specified pickup
delay.
The FlexElement 1 has picked up
The FlexElement 1 has operated
The FlexElements 2 to 8 is the same as Flexelement.
Pickup accumulator 1 (7) when the frequency is outside the specified
frequency band or limit
Operate accumulator 1 (7) when the frequency OOB accumulation
exceeds the specified Time Limit
Generated upon activation of any target message
Pushbutton [X] has been turned on
Pushbutton [X] has been turned off
Testing is enabled
Testing is disabled
^^ - content between the two ^ changes according to what is
programmed in the noted Operand Custom Text register
FLEXLOGIC
4–375