PROTECTION
4–190
REVERSE LIMIT ANGLE
Range: 40° to 90° in steps of 1°
Default: 90°
This setting defines a symmetrical (in both directions from the ECA) limit angle for the
reverse direction.
REVERSE PICKUP
Range: 0.050 to 30.000 x CT in steps of 0.001 x CT
Default: 0.050 x CT
This setting defines the Pickup level for the overcurrent unit of the element in the reverse
direction.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Self-reset
889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL