Field settings
2.12

I-Demand Function

1
Purpose
Setting
3
4
5
4–26
Set a limitation towards the power consumption from the system.(e.g. budget control, limit power
consumption during peak moments,..)
3 different demand setting can be selected by using terminal X801M:
Demand 1 → Close contact between COM and contact 1
Demand 2 → Close contact between COM and contact 2
Demand 3 → Close contact between COM and contact 3
Power supply connector
(on outdoor PCB X77A)
ESIE05-03
Transmission connector
(on outdoor PCB X6A)
Output on X801M =
12VDC, 12mA
Maximum wire length =
100 meter