6.1.11 Configuring the Connection (Cnct) Setting

EPM 2200 POWER METER – INSTRUCTION MANUAL
4.
Press ENTER again to select the to Pt-S (PT scaling) value.
The Pt-S value can be "1", "10", or "100". Refer to Programming the Configuration Mode
Screens on page 7–7 for instructions on changing values.
Example settings for the Pt-n, Pt-d, and Pt-S values are shown below:
277/277 Volts:
14400/120 Volts:
138000/69 Volts:
345000/115 Volts:
345000/69 Volts:
5.
Press ENTER to scroll through the other CFG parameters.
6.
Press DOWN or RIGHT to display the password screen (see Reset Mode on
page 7–4 for details).
7.
Press MENU to return to the Main Configuration Menu.
Pt-n and Pt-S are dictated by primary voltage.
Pt-d is secondary voltage.
Use the following procedure to program the connection (Cnct) setting.
1.
Push the DOWN Button to scroll through the Configuration Mode parameters:
Scroll, CT, PT, Connection (Cnct), and Port. The "active" parameter is in the A
screen and is flashing
Pt-n value is 277, Pt-d value is 277, Pt-Multiplier is 1
Pt-n value is 1440, Pt-d value is 120, Pt-S value is 10
Pt-n value is 1380, Pt-d value is 69, Pt-S value is 100
Pt-n value is 3450, Pt-d value is 115, Pt-S value is 100
Pt-n value is 345, Pt-d value is 69, Pt-S value is 1000
PROGRAMMING USING THE FACEPLATE