2.4

Accuracy

Voltage L-N [V]
Voltage L-L [V]
Current Phase [A]
Current Neutral (calculated)
[A]
Active Power Total [W]
Active Energy Total [Wh]
Reactive Power Total [VAR]
Reactive Energy Total [VARh]
Apparent Power Total [VA]
Apparent Energy Total [VAh]
Power Factor
Frequency
Load Bar
Note
EPM 2200 POWER METER – INSTRUCTION MANUAL
For 23
C, 3 Phase balanced Wye or Delta load.
°
Parameter
0.2% of reading
0.4% of reading
0.2% of reading
2% of Full Scale
0.5% of reading
0.5% of reading
1.0% of reading
1.0% of reading
1.0% of reading
1.0% of reading
1.0% of reading
+/- 0.01Hz
+/- 1 segment
1
For 2.5 element programmed units, degrade accuracy by an additional 0.5% of reading.
2
For unbalanced voltage inputs where at least one crosses the 150V auto-scale threshold
(for example, 120V/120V/208V system), degrade accuracy by additional 0.4%.
EPM 2200 accuracy meets the IEC62053-22 Accuracy Standards for 0.5% Class Meters.
This standard is shown in the table below.
Value of Current
0.01 I
n
≤ I < 0. 05 I
n
n
max
0.05 I
≤ I ≤ I
n
n
0.02 I
≤ I < 0.1 I
n
max
0.1 I
≤ I ≤ I
When specially requested by the
user, from:
n
max
0.1 I
≤ I ≤ I
In the table above:
I
= Nominal (5A)
n
I
= Full Scale
max
Accuracy
2
(69 to 480)V
(120 to 600)V
1
(0.15 to 5)A
1
(0.15 to 5)A @ (45 to 65)Hz
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0.5 to 1) lag/lead PF
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0.5 to 1) lag/lead PF
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0 to 0.8) lag/lead PF
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0 to 0.8) lag/lead PF
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0.5 to 1) lag/lead PF
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0.5 to 1) lag/lead PF
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0.5 to 1) lag/lead PF
(45 to 65)Hz
1
(0.005 to 6)A
Power Factor
Percentage Error Limits for
1
±1.0
1
±0.5
0.5 inductive
±1.0
0.8 capacitive
±1.0
0.5 inductive
±0.6
0.8 capacitive
±0.6
0.25 inductive
±1.0
0.8 capacitive
±1.0
ACCURACY
Accuracy Input Range
Meters of Class 0.5 S