Current -Only Measurement (Single -Phase ) - GE Multilin EPM 2200 Instruction Manual

Power
Hide thumbs Also See for Multilin EPM 2200:
Table of Contents

Advertisement

CHAPTER 4: ELECTRICAL INSTALLATION
4.2.11 (10) Current-Only Measurement (Single-Phase)
LINE
A
N
N
A
LOAD
Note
EPM 2200 POWER METER – INSTRUCTION MANUAL
For this wiring type, select 3 EL WYE (3 Element Wye) in the meter programming setup.
CT
Shorting
Block
Earth Ground
Figure 4-16: Current-Only Measurement (Single-Phase)
Even if the meter is used only for current measurement, the unit requires a AN volts
reference. Please ensure that the voltage input is attached to the meter. AC control power
can be used to provide the reference signal.
ELECTRICAL CONNECTION DIAGRAMS
HI
HI
HI
lc
lb
la
LO
LO
LO
Power
Supply
Connection
GND
FUSE
L(+)
L(+)
N(-)
3A
N(-)
Vref
Va
20VAC
FUSE
Minimum
Vb
Vc
0.1A
4–19